Remko rvs...h (inox) – REMKO RVS 60 H User Manual
Page 22
Connection of the
medium lines
■
The connection of the lines
on-site takes place on the front
side of the unit.
■
For the purpose of servicing,
connections must be equipped
with shut-off valves and valves
for hydronic balancing.
■
Additional automatic bleed
valves are to be provided in the
supply and return at the instal-
lation's highest point.
■
The medium lines must not
exert any structural load on the
unit.
■
The line connections may not
generate any thermal or
mechanical stress on the unit.
If necessary, the lines should be
independently supported.
■
If the unit is at first to be operated
with only a part of the
entire system, the medium
flow volume for the missing
system components are to be
simulated using the volume
control valve.
■
The pipe size must not restrict
the minimum medium flow.
Installation of the safety valve
The standard safety valve is not in-
stalled. Position the valve as shown
in the illustration and carry out
the correct installation of the drain
line. Local disposal
regulations must be observed if
glycol is used.
Pipe routing
RVS 60H / RVS 75H
free pipe
routeing
possible
free pipe
routeing
possible
no pipe
routeing possible
RVS 100H / RVS 150H
Necessary system components
No pipe r
outeing possible
No pipe r
outeing possible
No pipe routeing
possible
A permanent large flow volume
must be ensured to realise the
minimum medium flow.
!
CAUTION
Position safety valve
RVS 60H to RVS 150H with medium storage tank (hydr. compensator)
RVS 60H to RVS 150H
Diagram of the System components
Legend:
1
Flow switch
2
Dirt trap
3
Shut-off valve
4
Compensator
5
Pressure gauge
6
Emptying
7
Automatic bleeding valve
8
Safety valve
1
7
8
8
6
9
9
5
13
13
4
4
12
14
15
3
3
11
11
2
10
10
1
7
8
6
9
5
13
4
4
12
14
15
3
3
11
2
10
10
9
Circulation pump
10 Valve for hydronic balancing
11 Diaphragm expansion vessel
12 Plate heat exchanger (evaporator)
13 Medium storage tank
14 Probe medium intake
15 Probe medium outlet
shippment
shippment
provided by the customer
provided by the customer
REMKO RVS...H (INOX)
22