Remko rvs...h (inox) – REMKO RVS 60 H User Manual
Page 10
Target value cooling mode
Programming target values
The target value cooling (r 01) and the actual (hysteresis) cooling (r 02)
can be displayed and changed under the menu item “-r-” without the
use of a password.
With the Key-Pad
▲ or ▼ the value can be changed within limits.
r 01 = 12.0 °C
Target value cooling mode (factory setting)
r 02 = 2.0 °C
Hysteresis cooling mode (factory setting)
Minimum target value cooling mode
10.0 °C
Maximum target value cooling mode
28.0 °C
Target value heating mode
The target value heating (r 03) and the hysteresis heating (r 04) can be
displayed and changed under the menu item “-r-” without the use of
a password.
With the Key-Pad
▲ or ▼ the value can be changed within the limits set
in the factor (r15 + r16).
r 03 = 40.0 °C
Target value heating mode (factory setting)
r 04 = 2.0 °C
Hysteresis heating mode (factory setting)
Minimum target value heating mode
15.0 °C
Maximum target value heating mode
45.0 °C
Password
Password
Display
Display
Submenu
Submenu
Submenu
Submenu
short-term
short-term
min. 5 sec.
+
...
repeated
short-term
short-term
short-term
short-term
Target value cooling
Target value cooling
old target value
old target value
new target value
new target value
short-term
short-term
min. 5 sec.
+
...
...
repeated
short-term
short-term
short-term
short-term
REMKO RVS...H (INOX)
10