REMKO RVS 60 H User Manual

Page 17

background image

Fault indicated by code

Code Fault type

Re-set

Intake type

Cut-off

Intake value

Automatic

Manual

Digital

Analog

Compr

essors

Condenser

fan

Cir

culation pump

A1

Antifreeze alarm medium cycle

B2

P05

OWT 13/11

x

x

AHt

Excess temperature at start

B1 / P16

x

IWT

10

x

x

ALt

Insufficient/or excess temperature at start C/H

B1 / P19

x

IWT

10

x

x

CP1

Compressor 1

x

x

E1

Temperature sensor medium intake defective

B1

x

IWT

10

x

x

x

E2

Temperature sensor medium output defective

B2

x

OWT 13/11

x

x

x

E3

Temperature sensor condenser defective

B3

x

PT

14/12

x

x

x

E4

Pressure tranceducer cooling cycle defective

Bn/V+

x

PS

Bn/V+

EHS

High supply voltage controller

x

x

x

x

ELS

Low supply voltage controller

Tr

x

x

x

x

EP1

EEPROM driver defective

x

x

x

x

EPb

EEPROM fault at start

Config.

x

x

x

x

EPr

EEPROM fault during operation

Config.

x

x

x

x

FL

Flow monitor has responded

ID1

x

FS

6/9

x

x

x

Hc1

Maintenance interval compressor 1

C14

x

Ht

Excessive temperature medium cycle

B1 / P16

x

IWT

10

HP1

Pressure switch HD cooling cycle

ID3

<3/hrs <3/hrs HP

2

x

on 1 min.

HP1

Tranceducer cooling cycle excess pressure

Bn/V+

x

PS

Bn/V+

x

x

x

LP1

Pressure switch ND cooling cycle

ID4

<3/hrs <3/hrs LP

3

x

x

tC1

Overload cycle 1

P08-13

x

x

x

tEr

Communication cabled remote control

x

x

x

x

tP

General overload

P08-13

x

x

x

x

Reports
LA

General reports

P08

x

D1

Report defrosting

x

dF1-2 Defrost cycle exceeded

Defrosting

period

x

x

x

Reset

1. Faults with automatic reset:

The reset is carried out automatically.

2. Faults with manual reset:

The reset can only be carried out by a specialist after the fault has been corrected.

3. Faults with semi-manual reset: The reset is first carried out automatically, afterwards only a manual reset is possible

by a specialist, after the fault has been corrected.

Fault

Code

Possible cause

check

Remedial measures

The unit

does not

start or

switches

itself

off.

ELS/EHS

Low/High supply voltage

controller

Initial voltage transformer, or mains

inlet voltage

Have checked by a

specialist.

EP1

EEprom controller error

Does the controller operate properly?

Have specialist check regulation or

parameters.

EPr

EEprom controller error

Does the controller operate properly?

Have specialist check regulation or

parameters.

Malfunctions

17