Orion System Zoning User Manual

Page 27

background image

Orion Systems

27

Zoning Design Guide

System Manager

24 VAC Supply Voltage (6 VA)
and Communications Loop
Use Prefabricated Modular Cable

VAV/Zone Controller

24 VAC Supply Voltage (6 VA)
and Communications Loop
Use Prefabricated Modular Cable

Modular Room Sensor
Use Prefabricated Modular Cable

Sensor Wiring
Orion temperature sensors utilize a type III thermistor
element that is one of the most commonly used sensors
in the building controls industry. The sensor wire should
be a minimum of 24 gauge however larger wire such as
18 gauge is commonly used. The exception to this is
the VAV/Zone Controller utilizes a Modular Room Sen-
sor which is connected with a prefabricated modular
cable.

Conventional thermostat cable is acceptable in most
commercial and institutional installations. In some in-
stallations which have the potential for high electrical

noise, such as broadcast facilities (radio, TV, etc.), heavy
industrial (machinery, welding equipment, etc.), and
medical (x-ray, scanning, etc.), it is advisable to use
shielded cable on sensors which are located in or close
to these environments. The same cable used for the com-
munication bus can be used in these situations.

Sensor requirements are:

Supply Air Sensor
(2) Conductors 24 gauge minimum

Return Sensor
(2) Conductors 24 gauge minimum

Outside Air Sensor
(2) Conductors 24 gauge minimum

Standard Room Sensor (HVAC Unit
Controllers Only)
(2) Conductors 24 gauge minimum
(3) Conductors if using optional slide
adjust

Modular Room Sensor (used with VAV/
Zone Controllers Only)
Use Prefabricated Modular Cable