Design considerations – Orion System Zoning User Manual
Page 12

12
Orion Systems
Zoning Design Guide
Design Considerations
Load Diversity
A zoning system is designed to improve tenant comfort
by dynamically rebalancing the air distribution when
used with a typical constant volume rooftop heating/
cooling unit. If zones with extremely different load con-
ditions are serviced by a single rooftop unit, the result
will be poor control and excessive wear due to cycling
of the equipment.
It is especially important to avoid mixing interior zones
(which require cooling all year) with exterior zones
(which may require constant heat during winter months).
If you must mix zones under these conditions, consider
using either VAV boxes with heat or separate external
heat on perimeter zones. Orion Zoning systems offer a
variety of methods to control additional zone heat to
help you avoid problems.
Group similar loads on an individual unit and use more
than one zoned unit if required. Any special loads can
be handled by using separate constant volume units.
The Orion Plus system offers the designer considerable
flexibility by allowing both multiple-zoned units and
single-zone units to be connected within a single simple
system.
Cooling - Partial Load Conditions
The engineer must be aware of several potential prob-
lems when applying a zoning system for cold weather
operation.
1.) Low Ambient Temperature Lockout. During very
cold weather it is common for mechanical systems to
have “low temperature lockouts” which protect equip-
ment from damage if operated under these conditions.
Orion also provides user programmed lockouts for pro-
tection purposes, although mechanical safeties should
always be used as the final stage of protection.
If the rooftop unit services interior zones with thermal
loads, which require cooling when outside temperatures
are below the safe operating limits for your equipment,
you should seriously consider installing an economizer
on your rooftop unit. The Orion control system is de-
signed to take advantage of an economizer if it is in-
stalled. The use of an economizer will save money on
utilities and provide comfort under conditions when it
is not possible to operate the mechanical cooling sys-
tem.
2.) Low Supply Air Temperatures. Under lightly
loaded conditions much of the supply air may be by-
passed back into the return air side of the HVAC unit.
This bypassing will result in the lowering of the supply
air temperature, which may result in the supply air tem-
perature reaching the low temperature safety limit. If
the supply air low temperature safety limit is exceeded,
the control system will “cut off” the mechanical cool-
ing to protect it from damage. Excessive cycling of the
mechanical system will result if this condition persists.
Comfort may also suffer if the system cannot run long
enough to satisfy cooling demands.
A number of things can be done to reduce this problem.
Some of these things depend upon the type of installa-
tion.
Avoid oversizing the unit. Do the system load calcula-
tions carefully. Since the zoning system directs the heat-
ing or cooling to the zones which require it, you may
find that you can use a smaller unit in many cases. Over-
sizing is the number one cause of excessive low supply
air temperature cycling.
Always specify that the unit is equipped with hot gas
bypass on the first stage of cooling. This will allow the
evaporator coil to operate at minimum loads without
the system cycling due to low temperature or pressure
safety limits and will in turn maintain the supply air
discharge temperature within a preferred range.
Use an economizer. Although this is not a cure-all, it
greatly improves operation during cool weather when
cooling loads are minimal. Using an economizer also
improves ventilation and lowers operating costs.
Increase cooling minimum airflow. Increase your cool-
ing minimum airflow or damper position settings to al-
low more air during cooling operation. Be careful to
avoid minimum settings that are so high they may cause
over cooling of the spaces.
Bypass the air into the ceiling plenum. If you have a
system without ducted return, bypass the air into the