beautypg.com

Zoning design procedures, 18 orion systems zoning design guide, Step #6 - sizing zone dampers – Orion System Zoning User Manual

Page 18

background image

18

Orion Systems

Zoning Design Guide

Fan

RA Sensor

SA Sensor

Return Air Duct

Supply Air Duct

SP Pickup

Bypass Damper

SP Sensor

Figure 1-10: Least Desirable Sensor Location

If the supply duct comes directly from the unit and im-
mediately splits in opposite directions, the pressure
pickup should be located ahead of the split, or as close
to it as possible, even if the bypass damper(s) are lo-
cated downstream of the split.

Step #6 - Sizing Zone Dampers

Use a load program to determine the peak load for each
zone. These calculations will be used in selecting the
appropriate zone damper sizes.

Using the maximum acceptable velocity for a branch
duct (typically 1000-1500 FPM for minimal noise), find
the smallest damper that will deliver the required CFM
as determined by the load program.

Locate the branch velocity used in the duct design pro-
gram on the left hand column of either the round or
rectangular damper sizing chart (Table 1-1 or Table 1-
2). Move across the chart and find the damper which
will provide the acceptable CFM to meet your specific
zone requirements.

Note

Compare the damper size selected against
the duct size to determine if the next size
up or down will provide acceptable
performance without requiring a transi-
tion fitting.

The master zone damper can have up to 2 additional
dampers slaved together with it for large zones. This
should be reserved for situations when it is not practi-
cal to use a single large damper. Each zone damper must
be sized for an equal portion of the total CFM required
for the zone. The slaved zone(s) track the master zones
modulation, therefore only pressure dependent control
is allowed when zone dampers are slaved.

Fan

RA Sensor

SA Sensor

3D

Min.

2D

Min.

Return Air Duct

Supply

Air

Duct

SP Pickup

Bypass Damper

SP Sensor

Fan

RA Sensor

SA Sensor

Return Air Duct

Supply Air Duct

Tubing To Be Equal

Length And Size

Bypass Damper

SP Sensor

SP Pickups

If the trunk ducts are properly sized for minimum pres-
sure drop, the location of the static pickup probe is not
particularly critical. It should ideally be located at right
angles to the airflow in a straight section of the supply
duct approximately 2/3 the distance of the total length
of the supply duct. Also the probe should be located
not less than 3 duct diameters downstream and 2 duct
diameters upstream of any elbow or takeoff. See Fig-
ure 1-8.

Figure 1-8: Preferred Sensor Location

Figure 1-9: Acceptable Sensor Location

Since the “ideal” location is often difficult to find in an
installation, a location in the main trunk where the tip
is not in a “negative pressure area” (e.g. just downstream
of the inside curve of an elbow) or an area where the
tube opening is directly impacted by the velocity of the
supply air. See Figure 1-9.

Zoning Design Procedures