Zoning design procedures, 20 orion systems zoning design guide, Table 1-1: round damper selection data – Orion System Zoning User Manual

Page 20

background image

20

Orion Systems

Zoning Design Guide

Zoning Design Procedures

Bypass Dampers

Zone Dampers

1/2" Foil Faced

Insulation

Actuator

Round Damper

Blade Assembly

Control Enclosure

(Cover Removed)

AIR

FLO

W AIR

FLO

W

Bypass & Slave Interface

1/2" Foil Faced

Insulation

Actuator

Zone Controller

Round Damper

Blade Assembly

Control Enclosure

(Cover Removed)

AIR

FLO

W AIR

FLO

W

1/2 " Fo il Face d
Insu lation

A ctuator

R oun d D am per
B lade Asse m bly

C ontrol E nclosu re

(C o ver R e m oved )

Slave Dampers

Table 1-1: Round Damper Selection Data

Damper Round Duct Size

(Area Ft

2

)

6”

(0.188)

8”

(0.338)

10”

(0.532)

12”

(0.769)

14”

(1.050)

16”

(1.375)

CFM @ 1” Velocity Pressure

Air Flow Probe “K” Factor- For Pressure

Independent Applications Only

474

950

1417

2120

2908

3700

Velocity Through Zone Damper

FPM

Airflow Through Zone Damper - CFM

(

∆P

S

inches W.C. With Air Damper Full Open)

750

141

(0.03)

254

(0.02)

399

(0.01)

577

(0.02)

788

(0.01)

1031

(0.01)

1000

188

(0.05)

338

(0.03)

532

(0.02)

769

(0.03)

1050

(0.02)

1375

(0.01)

1250

235

(0.07)

423

(0.04)

665

(0.03)

961

(0.04)

1313

(0.03)

1718

(0.02)

1500

282

(0.09)

507

(0.06)

798

(0.04)

1154

(0.05)

1575

0.04)

2062

(0.03)

1750

329

(0.12)

592

(0.08)

931

(0.06)

1346

(0.06)

1838

(0.05)

2405

(0.04)

2000

376

(0.15)

676

(0.10)

1064

(0.07)

1538

(0.07)

2100

(0.07)

2749

(0.05)

2250

423

(0.18)

761

(0.13)

1197

(0.09)

1730

(0.09)

2363

(0.08)

3094

(0.06)