Troubleshooting, Lat sensor testing, Preheat-x technical guide 24 – Orion System PREHEAT-X User Manual
Page 24: Leaving air temperature sensor

TROUBLESHOOTING
PREHEAT-X Technical Guide
24
LAT Sensor Testing
Leaving Air Temperature Sensor
If you suspect the Leaving Air Temperature Sensor is not reading
correctly, make sure the wiring terminal connections are tight and
that any wiring splices are properly connected. You can check the
operation of the Leaving Air Temperature Sensor by measuring
the resistance or voltage using a digital multimeter. Set the meter
to DC Volts. Place the positive probe on the AIN terminal and the
negative probe on the GND terminal. Read the DC Volts and fi nd
that voltage in Table 3.
Read the temperature corresponding with that voltage and determine
if this is close to the actual temperature the sensor is exposed to. If the
temperature from the chart is different by more than a few degrees,
you probably have a defective or damaged sensor. You can also
check the sensor resistance to determine correct operation. To read
the resistance, set the meter to Ohms. Unplug the sensor connector
from the board and measure the resistance across the disconnected
wires. This resistance should match the corresponding temperature
from Table 3.
Temperature to Resistance/Voltage Chart
Temp
(
°F)
Temp
(
°C)
Resistance
(Ohms)
Voltage @
Input (VDC)
-10
-23.3
93333
2.98
-5
-20.6
80531
2.94
0
-17.8
69822
2.89
5
-15.0
60552
2.83
10
-12.2
52500
2.77
15
-9.4
45902
2.71
20
-6.7
40147
2.64
25
-3.9
35165
2.57
30
-1.1
30805
2.49
35
1.6
27140
2.41
40
4.4
23874
2.33
45
7.2
21094
2.24
50
10.0
18655
2.15
52
11.1
17799
2.11
54
12.2
16956
2.08
56
13.3
16164
2.04
58
14.4
15385
2.00
60
15.6
14681
1.96
62
16.7
14014
1.93
64
17.8
13382
1.89
66
18.9
12758
1.85
Temperature to Resistance/Voltage Chart
Temp
(
°F)
Temp
(
°C)
Resistance
(Ohms)
Voltage @
Input (VDC)
68
20.0
12191
1.81
69
20.6
11906
1.79
70
21.1
11652
1.78
71
21.7
11379
1.76
72
22.2
11136
1.74
73
22.7
10878
1.72
74
23.3
10625
1.70
75
23.9
10398
1.68
76
24.4
10158
1.66
78
25.6
9711
1.63
80
27.8
9302
1.59
82
27.8
8893
1.55
84
28.9
8514
1.52
86
30.0
8153
1.48
88
31.1
7805
1.45
90
32.2
7472
1.41
95
35.0
6716
1.33
100
37.8
6047
1.24
105
40.6
5453
1.16
110
43.3
4923
1.09
115
46.1
4449
1.02
120
48.9
4030
.95
125
51.7
3656
.88
130
54.4
3317
.82
135
57.2
3015
.76
140
60.0
2743
.71
145
62.8
2502
.66
Table 3: 0-3.3 V Temperature Sensor - Voltage &
Resistance for Type III Sensors
Table 3, continued: 0-3.3 V Temperature Sensor -
Voltage & Resistance for Type III Sensors
Thermistor Sensor Testing Instructions
1.) Use the resistance column to check the thermistor sensor while
disconnected from the controllers (not powered).
2.) Use the voltage column to check sensors while connected to
powered controllers. Read voltage with meter set on DC volts. Place
the “-” (minus) lead on GND terminal and the “+” (plus) lead on the
sensor input terminal being investigated.
If the voltage is above 3.3 VDC, the sensor or wiring is “open.” If
the voltage is less than 0.05 VDC, the sensor or wiring is shorted.