Page 20: Communication confi guration screens

background image

LCD DISPLAY SCREENS

PREHEAT-X Technical Guide

20

COMM MODE

BACNET, EBUS,

S-ALONE

COMMUNICATION MODE

This setting confi gures the communications mode. The choices are (1)

BACNET, (2) EBUS, or (3) S-ALONE (default).

Communicating Confi guration Screens

MAC ADDR

0-128

BAC ID

0-30,000

BACnet

®

- CURRENT MAC ADDRESS

Valid range is 0 to 128. Default is 0.

BACnet

®

- CURRENT ID Start

Range is 0-30,000. Default is 15,000..

BAC BAUD

38400

BACnet

®

- CURRENT BAUD RATE

9600, 19200, 38400, 57600, 76800. Default is 38400.

Communication Confi guration Screens

Refer to the following map when navigating through the Commu-
nicating Confi guration Screens. From the COM CONFIG Screen,
press

to scroll through the screens and change setpoints.

Use the

and

arrow keys to change your selections.

Press

to save any changes.

COMM

CONFIG

E-BUS CFG

VCM-X, VCB-X,

VCC-X or NONE

E-BUS CONFIGURATION

Select the type of controller that the PREHEAT-X is connected to. The

choices are VCM-X, VCB-X, VCC-X, or NONE (default). NOTE: You

must cycle power after changing this setting.