beautypg.com

Addressing & powering up, General, Controller addressing – Orion System Modular VAV/Zone Controller User Manual

Page 17: Power wiring, Start-up & commissioning

background image

Addressing & Powering Up

Figure 17: Address Switch Setting

General

In order to have a trouble free start-up, it is important to follow a few

simple procedures. Before applying power for the first time, it is very

important to correctly address the controller and run through a few

simple checks.

Controller Addressing

All Modular VAV/Zone Controller Actuator Packages are equipped

with address switches. If the Modular VAV/Zone Controller Actuator

Package is to operate as a Stand Alone controller (not connected to any

other HVAC unit or VAV/Zone Controller(s)), the controller address

switch should be set for address 1. When the Modular VAV/Zone Con-

troller Actuator Package is to be connected to other Modular VAV/Zone

Controller Actuator Packages on a communication loop, each Modular

VAV/Zone Controller Actuator Package’s address switch must be set

with a unique address between 1 and 58.

When programming the Modular VAV/Zone Controller Actuator Package

on a Stand Alone or Interconnected System and you are asked to enter

the Unit ID, you would enter the address for the controller you wish to

program. When programming the Modular VAV/Zone Controller Actua-

tor Package on a Networked System and you are asked to enter the Unit

ID, you would first enter the MiniLink PD loop address for the loop the

Modular VAV/Zone Controller Actuator Package is connected to and then

enter the Modular VAV/Zone Controller Actuator Package’s address. See

Figure 17 for a diagram depicting address switch settings.

For detailed information regarding communication wiring and connec-

tion for Interconnected and Networked systems, please see the Orion

System Installation & Troubleshooting Guide.

Power Wiring

One of the most important checks to make before powering up the system

for the first time is to confirm proper voltage and transformer sizing for

the Power/Comm board that is connected to it. Each Modular VAV/Zone

Controller Actuator Package requires 6 VA of power delivered to it at 24

VAC. See page 15 of this manual for complete wiring and transformer

sizing information for the VAV/Zone Controller and its associated Power/

Comm board. All VAV/Zone Controllers must be connected to a Power/

Comm board using prefabricated modular cables.

Check all modular connectors to be sure they are completely pushed and

locked into their mating connectors. Confirm that all sensors required

for your system are mounted in the appropriate location and that the

modular cables are plugged into the correct connectors on the Modular

VAV/Zone Controller Actuator Package. Check the actuator cable and

be sure it is plugged in and secured to the modular connector on the

actuator and the Modular VAV/Zone Controller Actuator Package circuit

board modular connector. Check that the Modular Room Sensor modular

connector is connected to one end of the modular sensor cable and the

other end is connected to the modular sensor connector on the Modular

VAV/Zone Controller Actuator Package. Be sure any Expansion Modules

connected to the Modular VAV/Zone Controller Actuator Packages are

also correctly wired per the Expansion Module wiring instructions on

pages 10 through 14 of this manual.

After all the above wiring checks are complete, apply power to the Power/

Comm board that is connected to the Modular VAV/Zone Controller

Actuator Packages.

17

Modular ZCAP Technical Guide

Start-Up & Commissioning

This manual is related to the following products: