Installation & wiring, Vcm-x modular e-bus controller technical guide, Gtc116 series, greentrol – Orion System VCM-X Modular E-BUS User Manual
Page 35: Ga-200-n series, and paragon microtrans, Greentrol, Vcm-x e-bus controller
VCM-X Modular E-BUS Controller Technical Guide
INSTALLATION & WIRING
35
Air Flow Monitoring Station Installation and Wiring
Figure 32: OE365-15-EBA - EBTRON
®
GTC116 Series, GreenTrol
TM
GA-200-N Series, and Paragon
MicroTrans
EQ
Series Air Flow Measurement Digital Transmitter Wiring
COMM
COMM
NET-
NET-
NET+
NET+
Airflow Measurement
Digital Transmitter Terminals
For Outdoor Air CFM
(Set Address Switch To 9)
Airflow Measurement
Digital Transmitter Terminals
For Return Air CFM
(Set Address Switch To 10)
Airflow Measurement
Digital Transmitter Terminals
For Supply Air CFM
(Set Address Switch To 11)
COMM
NET-
NET+
VCM-X E-BUS Controller
OE365-15-EBA
E-BUS Adapter Board
HSSC Cable Connect To
VCM-X E-BUS Port
I2C DIGITAL
SENSOR
I2C
EXPANSION
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
WattMaster Label
#LB102033-01
AI1 AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
AI2
AI3
AI4
AI5
AI7
EMERGENCY SHUTDOWN
AI1 SET
AI1
THERM
THERM
4-20mA
0-10V
0-5V
ANALOG INPU
JUMPER
SETTINGS
HSSC Cable Connect To
VCM-X E-BUS Port
Connect To
VCM-X E-BUS Port
NOTE: Set Airflow Monitoring
Station’s Baud Rate To 9600
In Order To Communicate
With The VCM-X.
Air Flow Monitoring Station
Installation and Wiring
The OE365-15-EBA E-BUS Adapter Board is used to connect selected
Air Flow Monitoring Stations to the VCM-X Controller. Currently, there
are up to three Air Flow Monitoring Station options that are supported
in our standard software.
• EBTRON
®
– GTC-116 Series Air Flow Monitoring Station*
•
GreenTrol™ Automation – GA-200-N Module used with
any GF Series Air Flow Monitoring Station
•
Paragon MicroTrans
EQ
series Air Flow Monitoring Station
The wiring for all three Air Flow Monitoring Stations are the same and
are shown in Figure 32.
NOTE: The Airfl ow Station’s baud rate needs to be set to 9600
in order to communicate with the VCM-X Controller.
*NOTE: When confi guring the GTC-116 Series, be sure to set
the Parity to “NO PARITY, 1 STOP BIT.”
NOTE: Up to 3 EBTRON
®
, GreenTrol
TM
, or Paragon Airfl ow
Measurement Digital Transmitters can be attached to each Adapter
Board.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) may be required.