Installation & wiring, Outdoor air humidity sensor wiring, Vcm-x modular e-bus controller technical guide – Orion System VCM-X Modular E-BUS User Manual
Page 25: 25 outdoor air humidity sensor, Oa humidity sensor

VCM-X Modular E-BUS Controller Technical Guide
INSTALLATION & WIRING
25
Outdoor Air Humidity Sensor
The OE265-13 Outdoor Air Humidity Sensor is connected to the system
by wiring it to the AI1 input on the VCM-X Expansion Module. It must
be wired as shown in Figure 22 below for proper controller operation.
Outdoor Air Humidity Sensor Wiring
Warning: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the OA Humidity Sensor
or VCM-X Expansion Module.
Figure 22: OE265-13 – Outdoor Air Humidity Sensor Wiring
AI1
GND
Modular Cable
Connect To VCM-X
E-BUS Controller
Modular Cable
Connect To Next Expansion
Board (When Used)
24 VAC
GND
10 VA Minimum Power Required For
VCM-X Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Modules must be wired in such a way that the expansion
modules and the controller are always powered together. Loss of power to
the expansion module will cause the controller to become inoperative until
power is restored to the expansion module.
Jumpers Must Be
Set as Shown
For Correct
O-5 VDC
Operation
1 & 3 Are Off
2 & 4 Are On
Jumpers Must Be Set as
Shown For Normal
1, 2, 4, 5 & 6 Are Off
3 Is On
Operation Of Sensor
4-20 mA
Zero
Span
V
AC or DC
GND
0-5V or 0-10V
4
4
4
5
5
6
6
ON
ON
ON
3
3
3
2
2
2
1
1
1
4
ON
3
2
1
OA Humidity Sensor
VCM-X Expansion
Module
Jumper
Must
Be Set To
0-5V As
Shown
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
VCM
WA
RN
IN
G
OB
SE
RV
E
POLAR
IT
Y
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER
ONLY
WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01-A
Rev.: 1L
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= HOOD ON - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
www.aaon.com
www.orioncontrols.com
VCM-X Expansion Module
Orion No.:OE333-23-EM
AAON No.:
R69190
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
A3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= ECONOMIZER FEEDBACK
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
I