OnLine Power Power Wave 4 User Manual
Page 62

6005-145 Rev. A
5-9
< O T H E R D A T A >
T E M P E R A T U R E = X X C
D C V O L T A G E = X X X V d c
D I S
C H A R G E C U R R E N T = X X X A
The UP (↑) or DOWN (↓) keys have no function in this menu. The screen will go
back to MENU 3 – the REAL TIME DATA menu, when ENTER(←┘) is pressed.
5.10. Menu 9 – Reserve Data Menu
< R E S E R V E D A T A >
R E S E R V E F R E Q U E N C Y = X X H Z
R - N = X X X V a c S - N = X X X V a c T - N = X X X V a c
This menu is displayed when
REAL TIME DATA MENU,. It is a data display menu, which shows real time data
of the reserve input, such as, RESERVE FREQUENCY, R-N/S-N/T-N VOLTAGE,
etc., for the user’s reference. The phase to phase voltage display is also available
when reserve input is a delta (
△ ) connected source.
The UP (↑) or DOWN (↓) keys have no function in this menu. The screen will go
back to MENU 3 – the REAL TIME DATA menu, when ENTER (←┘) is pressed.
5.11. Menu 10 – Boost Charge Setting Menu
< B O O S T C H A R G E S E T T I N G >
→ A U T O - B O O S T ( M O N T H ) = 0 4
A U T O - B O O S T ( B A T T L O W ) = 0 8
C H A R G E C U R R E N T = L O E X I T