MIMIC DISPLAY UNDER NORMAL OPERATION
(e) Push inverter ON switch – To turn on the inverter, the inverter ON switch (
)
and
the control switch (
)
must be pressed simultaneously. The inverter will start
working and inverter output will be established in 4 seconds. The load will
automatically be transferred to the inverter 3 seconds later. Now the ELI is in
normal operation.
(f) Check if the mimic LED is correct, as shown in the figure, above. All warning
LEDs on the right side are off, two LEDs: ‘INVERTER ON’ and ‘INVERTER SS’
on the left side should be lit. If the load is over 70%, the ‘70% LOAD’ LED will
also be lit.
4.2. Shutdown Procedure
If you want to shutdown the ELI completely (no power at output or inside), please
follow the steps below.
(a) Switch off the inverter – The inverter can be switched off by pressing the inverter
OFF switch (
)
and the control switch (
)
simultaneously. The load will be
automatically transferred to reserve without interruption.