OnLine Power Power Wave 4 User Manual
Page 52

6005-145 Rev. A
4-5
(d)
Close the (optional) battery breaker – For safety purposes, a fuse is employed in
the battery to the DC bus. Now the battery will take-over to supply the DC bus if
the rectifier mains fail.
(e)
Push inverter ON switch – To turn on the inverter, the inverter ON switch (
)
and
the control switch (
)
must be pressed simultaneously. The inverter will start
working and inverter output will be established in 4 seconds. The load will
automatically be transferred to the inverter 3 seconds later. Now the ELI is in
normal operation.
4.5. Green Mode: customer selectable for green mode (fast transfer less than 2ms).
(a) Menu 1 – Select Menu
The Select Menu is for the user to select, via the cursor (→), the type of data the
user wants to view, such as, inverter on/off, buzzer on/off, charging time and
magnitude, date/time etc. The cursor (→) can be moved upward by the UP(↑) key,
and can be moved downward by the DOWN(↓) key. The selection is confirmed by
pressing the ENTER key (←┘), and change to the menu at which the cursor is
pointing. If the item “PARAMETER SET” is selected, the LCD will jump into a
screen which will ask the user to key in the password. See the figure below.
The password is a 4 digit number which can be changed upward or downward by the