beautypg.com

ONICON D-100 Flow User Manual

Page 6

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

D-100 Flow Display Manual 10/14 - 0634-14 / 18340

Page 6

GENERAL SPECIFICATIONS

ACCURACY

Analog Inputs: 0.1% of full scale

Analog Outputs: 0.1% of full scale

PROGRAMMING

Factory programmed for specific application.

MEMORY

Nonvolatile EEPROM memory retains all program

parameters and totalized values in the event of

power

loss.

DISPLAY

Standard: 2-line Alphanumeric LCD displays flow

rate and flow total for the standard flow input

Alpha: 16 character, 0.2” high

Numeric: 7 digit, 0.4” high

Rate Display Range: 0 - 9,999,999

Totalizer Display Range: 0 - ,999,999

The totalizers will roll over to zero when maximum

count is exceeded.

OUTPUT SIGNALS

Pulse Outputs:

Two isolated contact closure outputs for separately

totalizing forward and reverse flow from the

standard flow input. Contact duration: 0.5, 1, 2

or 6 seconds (factory selectable). Default: 0.5

seconds

Maximum contact ratings: 100 mA, 50 VDC

Isolated contact closure output for indicating flow

direction

Maximum contact ratings: 100 mA, 50 VDC

Analog Outputs Options:

Single isolated analog output:

4-20 mA, 0-10 V or 0-5 V

Multiple (4) isolated analog outputs: 4-20 mA,

0-10 V or 0-5 V outputs

Network Interface Options

MODBUS RTU RS485

MODBUS RTU TCP/IP

BACnet

MS/TP

BACnet

UDP/IP

LONWORKS

FTT10A

JCI Metasys - N2

Siemens Apogee - P1 FLN

INPUT SIGNALS

Standard:

One totalizing flow input:

4-20 mA, contact closure or pulse

One contact closure input for flow

direction

Optional:

Two auxiliary analog rate inputs:

4-20

mA

One digital totalizer input: pulse or

contact

closure

Totalizer Range: 0-9,999,999 counts.

Total will rollover to zero when

maximum count is exceeded.

TEMPERATURE RANGE

Ambient temperature range: -20° F to 140° F

Do not install in direct sunlight.

MAINTENANCE

ONICON recommends periodic inspection and

recalibration for sensors connected to the D-100.

No other periodic maintenance is required for the

main

unit.

MECHANICAL

Electronics Enclosure:

Standard: Steel NEMA 13, wall mount, 8”x10”x4”

Optional: NEMA 4

ELECTRICAL

This equipment is intended for INSTALLATION CATEGORY

(OVERVOLTAGE CATEGORY) II applications.

INPUT POWER:

Factory

Selectable:

24 VAC: 20 - 28V, 50/60 Hz, 500 mA

120 VAC: 108 - 132V, 50/60 Hz, 250 mA

240 VAC: 207 - 253V, 50 Hz, 250 mA

INTERNAL FUSE RATING:

24 VAC - 1 Amp Slo-Blo, 3AG Fuse

120 VAC - 1/4 Amp Slo-Blo, 3AG Fuse

240 VAC - 1/8 Amp Slo-Blo, 3AG Fuse

OUTPUT:

24 VDC, 250 mA maximum

OVERCURRENT PROTECTIVE DEVICE RATINGS:

Supply mains overcurrent protective devices with the

following

ratings:

120 VAC 50/60 Hz – 15 A

240 VAC 50 Hz – 6 A

WIRING:

Flow signals: Use 18-22 ga shielded cable – see flow

meter specification sheet or flow meter manual for

the correct number of conductors.

24 VAC input power: Use PVC jacketed copper cable

with a wire gauge suitable for the length of run and

required maximum current carrying capacity. The

installation must comply with all local, state and

federal

building

codes.

120/240 VAC input power: Use a three wire service with one

wire a protective earth ground. The installation must

comply with all local, state and federal building codes.

Note: Specifications are subject to change without notice.

!

WARNING

All electrical connections must be made in

accordance with the imformation provided

here. Failure to do so will result in an

increases risk of injury.