Operating from 24 VAC power
The D-100 can be factory configured to operate from 24 ±4 V 50/60 Hz power. Be sure to
connect a separate protective earth wire to the protective earth lug provided and shown
below.
Do not exceed 13 in-lb (1.5 Nm) of torque when tightening.
OHM 5%
3W
TB1
AMP
F1
1
H1
D3
D4
TB1
1/4 AMP
F1
VAR1
D2
D1
T1
LED1
20075-50 REV. A
R1
H3
R7
10
G
G
J2-12
+24
+15
J2-1
1
60
HZ
G
5
J1
L1 N
Not Used
L1 N
Not Used
Earth Connection
Input Power Connection