Caution, Flow meter inputs – ONICON D-100 Flow User Manual
Page 17
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
D-100 Flow Display Manual 10/14 - 0634-14 / 18340
Page 17
* 4-20mA +
* 24 VDC Supply +
F-5100 Flow Meter
Connections
Connections shown with * are required for
all installations.
* Supply Common -
Flow Meter Inputs
* Shield
* Earth
Inputs & Outputs Terminal #
* + 24V
* 4-20mA
B5
C5
* - Common
B6
* Earth
L1 N
Not Used
CAUTION
Shield and earth connections are required for proper operation. Failure to use shielded cable
or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields
should be terminated at the D-100 shield terminals and left unterminated at the flow meter.
!
3.3.1.7 ONICON F-5100 Series Flow Meters