ONICON D-100 Flow User Manual
Page 20
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
D-100 Flow Display Manual 10/14 - 0634-14 / 18340
Page 20
3.3.7 Totalizer Outputs and Mode Status
For unidirectional flow applications, the output relay for
flow total is located on the mother board at T1, terminals 1
and (+) 2 mode 1. The value of each “closure” is listed on
the configuration data sheet and is the same as the flow total
multiplier displayed on the LCD (example: each closure = 100
Gallons). This information is also included on a label inside
the D-100. For bi-directional flow applications, connections
for the (+) mode 1 flow total output relay are at T1 terminals 1
and 2. The (-) mode 2 flow total output relay connections are at
T1 terminals 3 and 4. Flow direction is indicated by the mode
status output (T1 pins 5 and 6). The table below describes the
relationship between (+) mode 1 and (-) mode 2 totals and
forward and reverse flow for ONICON insertion turbine and
inline electromagnetic flow meters. Do not exceed 4.5 in-lb (0.5
Nm) of torque, when tightening the terminals.
OUTPUTS
TOTALIZER OUTPUT
MODE 1
TOTALIZER OUTPUT
MODE 2
MODE STATUS
CHANNEL A
ANALOG OUTPUT
CHANNEL B
ANALOG OUTPUT
CHANNEL C
ANALOG OUTPUT
CHANNEL D
ANALOG OUTPUT
ALARM
OUTPUT
+
_
+
_
+
_
+
_
T1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Flow Meter
Model
Flow Direction
Relative to Direction
Arrow on Meter
Flow Meter
Output Condition
D-100 Mode
Status Indicator
(T1 - Pins 5 & 6)
D-100 Register
Accumulating
Totals
FB-1200 Series
Flow in the direction
of arrow
Closed contact
Open contact
+ Mode 1
FB-1200 Series
Flow reverse from
direction arrow
Open contact
Closed contact
- Mode 2
F-3000 Series
Flow toward (+) sign
Not energized
(open)
Closed contact
- Mode 2
F-3000 Series
Flow toward (-) sign
Energized
(closed)
Open contact
+ Mode 1
F-4000 Series
Flow forward (-) sign
Energized
(closed)
Open contact
+ Mode 1
F-4000 Series
Flow forward (-) sign
Not Energized
(open)
Closed contact
- Mode 2
3.3.8 Isolated Analog Outputs
The D-100 can be configured to provide up to four isolated analog outputs. These
outputs can be used to replicate the incoming analog signals. The output signal type
can be 4-20 mA, 0-10 VDC or 0-5 VDC and is field configurable. Contact ONICON for
assistance in reconfiguring or reprogramming the analog inputs. See the configuration
data sheet provided or the label located inside the D-100 for output specific configuration
information. Analog output signal connections are made at T1 terminals 7 through 14.
Do not exceed 4.5 in-lb (0.5 Nm) of torque, when tightening the terminals.
(+)
(-)