Caution, F-2000 flow meter connections, Flow meter inputs – ONICON D-100 Flow User Manual
Page 14: Auxiliary flow meter signals
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
D-100 Flow Display Manual 10/14 - 0634-14 / 18340
Page 14
* 4-20mA -
* 4-20mA +
F-2000 Flow Meter
Connections
(A) Scaled +
(A) Scaled -
Flow Meter Inputs
* Shield
Auxiliary Flow Meter Signals
* Earth
Outputs
Terminal #
* + 24V
* - ILoop
+ 24V
- Pout
* Earth
Connections shown with * are required for all installations. Connections shown with (A) are optional.
1
2
3
4
L1 N
Not Used
CAUTION
Shield and earth connections are required for proper operation. Failure to use shielded cable
or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields
should be terminated at the D-100 shield terminals and left unterminated at the flow meter.
!
3.3.1.4 ONICON F-2500 Flow Meters
F-2500 Flow Meter
Connections