Flow meter inputs, Auxiliary flow meter signals, Caution – ONICON D-100 Flow User Manual
Page 12: Shield, Earth (green/yellow), G60hz, Led1 t1, Var1
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
D-100 Flow Display Manual 10/14 - 0634-14 / 18340
Page 12
3.3.1.2
Input Signal Connections from F-3500 Flow Meter
3.3.1.3
Input Signal Connections from FB-3500 Flow Meter
J1
5
G
60HZ
1
J2-1
+1
5
+24
J2-12
G
G
10
R7
H3
R1
20075-50 REV. A
LED1
T1
D1
D2
VAR1
F1
1/8 AMP
TB1
D4
D3
H1
1
Connections shown for T5-1 and T5-2
are for the same analog output from the
FB-3500. This output can be configured in
the flow meter as a 4-20mA or 0 -10 VDC.
0-10 VDC + (Blue)
* Frequency - (Yellow)
* 24VDC Supply + (Red)
* Supply Common - (Black)
* Frequency + (Green)
FB-3500 Flow Meter Connections
Connections shown with * are required.
4-20mA + (Blue)
Flow Meter Inputs
* Shield
Auxiliary Flow Meter Signals
Isolated Analog Common - (Brown)
Earth (Green/Yellow)*
Factory Installed Cable
T4
1
2
3
4
5
6
7
8
9
10
11
12
13
* Direction - (White / Black)
* Direction + (Orange / Black)
T5
1
2
3
4
5
6
Alarm - (White)
Alarm + (Orange)
Connections shown below dashed line
are for flow meter output signals not used
by the BTU meter. Both incoming and
outgoing connections are made to the
same terminal.
L1 N
Not Used
!
CAUTION
See FB-3500 installation and operation guide for additional information on properly grounding the meter.
J1
5
G
60HZ
1
J2-1
+1
5
+24
J2-12
G
G
10
R7
H3
R1
20075-50 REV. A
LED1
T1
D1
D2
VAR1
F1
1/8 AMP
TB1
D4
D3
H1
1
Connections shown for T5-1 and T5-2
are for the same analog output from the
F-3500. This output can be configured in
the flow meter as a 4-20mA or 0 -10 VDC.
0-10 VDC + (Blue)
* Frequency - (Yellow)
* 24VDC Supply + (Red)
* Supply Common - (Black)
* Frequency + (Green)
F-3500 Flow Meter Connections
Connections shown with * are required.
4-20mA + (Blue)
Flow Meter Inputs
* Shield
Auxiliary Flow Meter Signals
Isolated Analog Common - (Brown)
Earth (Green/Yellow)*
Factory Installed Cable
T4
1
2
3
4
5
6
7
8
9
10
11
12
13
T5
1
2
3
4
5
6
Alarm - (White)
Alarm + (Orange)
Connections shown below dashed line
are for flow meter output signals not used
by the BTU meter. Both incoming and
outgoing connections are made to the
same terminal.
L1 N
Not Used
!
CAUTION
See F-3500 installation and operation guide for additional information on properly grounding the meter.
Connections shown below dashed line
are for flow meter output signals not
used by the D-100. Both incoming and
outgoing connections are made to the
same terminal.
Connections shown below dashed line are
for flow meter output signals not used by
the D-100. Both incoming and outgoing
connections are made to the same
terminal.