Important notes on installation

3.3

Product designation / Which model do you have

The product designation and the most important unit data are found on the rating plate fixed to the

evaporative module and the control unit.

Information regarding the rating plate and the product key can be found in the operation manual of the

Nortec ME Direct Feed.

3.4

UL approved installation

In order to maintain a UL approved installation, the following installation requirements must be met,

otherwise the Nortec ME system will not be approved under UL998.
1. The Nortec ME Direct Feed hydraulic manifold must be installed external to the air stream in accor-

dance with the typical installation drawing in chapter 4.1.2 – Typical installation Nortec ME Direct

Feed (external installation).

2. All interconnecting piping and connections between the evaporative module and the hydraulic ma-

nifold, in direct contact with the air stream must be either copper or stainless steel.

Note: water quality should be considered when selecting an appropriate material (i.e. copper is not

suitable for RO water).