Mounting the optional control unit

4.5.1 Notes on positioning the control unit

Please observe the following notes when positioning the optional Nortec ME control unit:
– The control unit can be mounted directly outside to the AHU/air duct or to a wall or stand (not sup-

plied).

– The control unit should ideally be positioned as close to the evaporative module as possible for ease

of servicing and maintenance.

– The control unit is protected according to

IP21. Make sure the control unit is installed in a drip-proof

location and the admissible ambient conditions are complied with (see technical data in the opera-

tion manual to the Nortec ME Direct Feed).

– The power supply to the control unit must be equipped with an electrical isolator (not supplied) fitted

within 1m (39") for purposes of maintenance and emergencies. When positioning the control unit

make sure the electrical isolator can be mounted within that range.