2 water installation (internal installation), Water installation (internal installation), 2 – water – Nortec ME Direct Feed Installation User Manual

Page 29: Installation (internal installation)

background image

29

Installation

4.4.2 Water installation (internal installation)

Stages

(box rows)

Connection layout

distribution hoses

2

2 1

4 2 1 3 5

3

2 1 3

4 2 1 3 5

4

4 2 1 3

4 2 1 3 5

5

4 2 1 3 5

4 2 1 3 5

Distribution hoses

ø15 mm (0.625")

constant slope

(no sagging)

Water supply push-fit

connector ø15 mm (0.625")

Feed through

Drain pipe ø54 mm (2.125")

with constant downslope

1...2 % (not supplied)

Shut-off valve

(supplied)

Drain trap (not supplied)

Drain trap height: Allow a height of 25 mm

(1") for every 250 Pa of duct pressure (eg.

100 mm (4") for 1000 Pa duct pressure)

Pipe feed through (by client)

Open tundish

(not supplied)

AHU drain with drain trap (not supplied)

Drain trap height: Allow a height of 25 mm

(1") for every 250 Pa of duct pressure (eg.

100 mm (4") for 1000 Pa duct pressure).

2...5 bar

Fig. 17: Water installation ME Direct Feed (internal installation)

Purge valve (option)