Parameter

Content in supply water

Concern

Total organic carbon

-

No specific concerns

Turbidity

< 5 NTU

No specific concerns

Colony count 22°C

< 1000 cfu/ml

Indicator of contaminated water supply

Coliform bacteria

< 10 cfu/100 ml

Indicator of poor water quality

Legionella bacteria

< 50 cfu/1000 ml

Risk of Legionella

Pseudomonas species

< 10 cfu/100 ml

Indicator of slime forming potential

Controlled Substances

DANGER!

Many of the following controlled substances are toxic; for example vinyl chloride is highly toxic, flam-

mable and carcinogenic and could be evaporated off the matrix and passed to the airflow. Therefore it

is important to note that any supply water coming from complex waste water, which may contain these

contaminates should therefore be carefully risk assessed by a water treatment specialist.

Controlled substances
Clostridium perfringens (including spores)
Acrylamide
Antimony
Arsenic
Benzene
Benzo(a)pyrene
Boron
Bromate
Cadium
Chromium
Cyanide
1,2-dichloroethane
Epichlorohydrin
Fluoride
Lead
Mercury
Nickel
Pesticides
Polycyclic aromatic hydrocarbons
Selenium
Tetrachloroethene and Trichloroethene
Trihalomethanes
Vinyl chloride

Water Monitoring
The Nortec ME water system must be monitored for hygiene as part of the maintenance programme.