5 | LS Installation Manual

System 3 - Multi-Zone System

Figure 4: Multi-zone System

Figure 3: Multi-zone System

Location

Advantages

Disadvantages

LOC. 1

Maximum absorption distance
to dampers.

Possible loss of capacity to
condensate on cooling coils.

LOC. 2

Heating coil will help absorb
steam.

Minimum distance to the
dampers could result in
wetting.

LOC. 3

Warm air.

Minimum distance to the
dampers could result in
wetting.

LOC. 4

Not recommended.

Filters may get saturated.
Cold air.

If one zone requires most of the air quantity supplied to the system, this zone should be the
location for the humidifier. Humidity will eventually equalize when the system has been in
operation for a while.