3 | LS Installation Manual
System 1 - Air Handling Unit
Figure 2: Air Handling Unit
Table 1: Air Handling Unit
Location
Advantages
Disadvantages
LOC. 1
MOST recommended.
Assuming there is
sufficient straight duct for
absorption.
High velocity may create long
absorption distances.
LOC. 2
Warm air from heating coil.
Good absorption will help
evaporate steam.
Cooling coils designed for
water.
Possible capacity drop due to
condensation on the coil.
LOC. 3
Warm air.
Good absorption.
If absorption distance is too
long it may wet the fan.
LOC. 4
Heating coils will help
evaporate steam.
Air is mixed well.
Absorption may be a problem.
No drain pan on heating coil.
Cold air.
LOC. 5
Not Recommended.
Filters may get saturated.
Cold air.
LOC. 6
Not Recommended.
Outside air may cause
condensation problems.
Problematic RH control.