3 | LS Installation Manual

System 1 - Air Handling Unit

Figure 2: Air Handling Unit

Table 1: Air Handling Unit

Location

Advantages

Disadvantages

LOC. 1

MOST recommended.
Assuming there is
sufficient straight duct for
absorption.

High velocity may create long
absorption distances.

LOC. 2

Warm air from heating coil.
Good absorption will help
evaporate steam.

Cooling coils designed for
water.
Possible capacity drop due to
condensation on the coil.

LOC. 3

Warm air.

Good absorption.

If absorption distance is too
long it may wet the fan.

LOC. 4

Heating coils will help
evaporate steam.

Air is mixed well.

Absorption may be a problem.

No drain pan on heating coil.

Cold air.

LOC. 5

Not Recommended.

Filters may get saturated.

Cold air.

LOC. 6

Not Recommended.

Outside air may cause
condensation problems.
Problematic RH control.