7 | LS Installation Manual

Steam and Condensate Piping

1 Steam supply must be taken from the top of the main supply to the humidifier. Do not take

from the sides or the bottom. See Figure 8.

2 For removal of condensate from the steam trap the condensate line should not be under

pressure. Nortec recommends a check valve be installed after the steam trap if the
condensate return line is pressurized.

3 Proper design and sizing of steam supply lines should be performed by a qualified firm.

Assembly Of Single Distributor Humidifier

Note: Follow all general instructions provided with valve and actuator.
All single distributor humidifiers will be assembled at the factory if the interconnecting piping
option is selected at time of order.

1 Match the separator/valve assembly with the correct distributor assembly (Nortec will tag

both assemblies).

2 The o-ring in the tube adaptor should be lubricated (use silicone based lubricant).
3 Slide the distributor into the tube adapter. Make sure that the o-ring is not damaged.

Tighten tube adapter. The adapter should be hand tightened plus ¼ turn (25 in-lbs ± 5 in-
lbs).

Figure 7: Single Distributor Humidifier

4 The union halves come together and are tightened to make a snug fit. The humidifier is

ready to be installed in the duct. Single tube comes factory assembled, multi-tube must be
field assembled.