Technical specifications (cont.) – MovinCool Office Pro W20 User Manual
Page 36
36
TECHNICAL SPECIFICATIONS (cont.)
• Specifications are subject to change without notice.
Note:
*1: If the entering water temperature is below 68 °F (20 °C) or above 86 °F (30 °C),
adjustment of the unit's water regulating valve setting is required.
*2: Measured at 3 feet (1.0 m) from surface of the unit.
ITEM
SPECIFICATIONS
Operating Condition Range
Inlet Air
Temperature
Max.
95 °F (35 °C), 60 %RH
Min.
65 °F (18 °C), 50 %RH
Entering Water
Temperature
*1
Max.
90 °F (32 °C)
Min.
40 °F (4.4 °C)
Water Pressure
150 psi (1,034 kPa) or less
Recommended Water
Flow Rate
5 gal/min (18 L/min)
Maximum Duct Length
Cold Duct
25 ft (7.6 m)
Sound Level
*2
High
62 dB (A)
Low
60 dB (A)
This manual is related to the following products: