29

INSPECTION & MAINTENANCE (cont.)

Water Regulating Valve

This unit is equipped with a water regulating valve to operate within wide water

temperature range. This water regulating valve automatically controls the water

flow rate to stabilize the refrigeration system and it has an adjusting bolt to adjust

the valve opening temperature.

Default Valve Setting and Operation Range

Default setting of the valve opening temperature is 86 °F (30 °C) and marked on

the valve housing. If the entering water temperature is below 86 °F (30 °C), there

is no loss of water while the unit is not operating. Adjustment of this valve setting

is required only when the unit will be used under the following conditions.

Entering water temperature is below 68 °F (20 °C):

Valve setting must be adjusted to lower temperature to extend the life of the

compressor.

Entering water temperature is above 86 °F (30 °C):

Valve setting must be adjusted to higher temperature to prevent wasted water.

Note: This adjustment expands the minimum water temperature range. Carefully

control the operating range.

CAUTION: Failure to adjust the water regulating valve or operating

the unit with entering water temperature below 68 °F (20 °C) without

adjusting the valve setting may damage the unit and void the

warranty. Contact a qualified technician for details.

ILL00205-00

ADJUSTING BOLT

WATER REGULATING
VALVE