Troubleshooting – MovinCool Classic Plus 14 User Manual
Page 31

31
TROUBLESHOOTING
Check the following items before calling your MovinCool reseller or a qualified
technician.
If conditions persist after the above actions have been taken, turn the unit off,
disconnect the power and contact your MovinCool reseller or a qualified
technician.
CONDITION
POSSIBLE CAUSE
REMEDY
Unit does not operate.
1. Ground fault breaker trip
or LCDI power cord trip.
Reset breaker or reset power
cord.
2. Drain tank is full.
(“TANK FULL” LED
flashes.)
Empty the drain tank.
3. High pressure switch
activated 10 times in 24
hours.
1. Clean air filter.
2. Check inlet and outlet air
to make sure that there
are no objects preventing
the air flow into or out from
the unit.
3. Check environmental
condition whether it is
within operation range or
not.
4. Reset controller.
To RESET: Press FAN HI/
LO and COOL ON/OFF
buttons simultaneously for
5 seconds, controller
returns to normal
operation.
Insufficient cooling.
1. Dirty/Blocked air filters.
Clean air filter.
2. Air inlet/outlet blocked.
Clean air inlet/outlet.
3. Improper temperature
setting.
Adjust temperature setting.