Condensate pump kit (optional for classic plus 26), Operation (cont.) – MovinCool Classic Plus 14 User Manual
Page 28

28
OPERATION (cont.)
Condensate Pump Kit (Optional for Classic Plus 26)
A condensate pump kit is available to allow continuous operation and to eliminate
the need for a drain tank.
When the water collects to level (A) in the
pump reservoir, the condensate pump
begins to operate and discharge the water.
When the water level drops below level
(B), the condensate pump stops.
Note: If for any reason the water level
exceeds that of level (A) in the pump reservoir, an overflow drain switch stops the
compressor operation, and the LCD displays "AS".
Note: If the fan mode control DIP switch (see page 24) is set to the STOP position,
the entire unit (including fan operation) turns off due to the over flow drain switch.
DISCHARGE HOSE
CONDENSATE
PUMP
RESERVOIR
CONDENSATE PUMP