28

OPERATION (cont.)

Condensate Pump Kit (Optional for Classic Plus 26)

A condensate pump kit is available to allow continuous operation and to eliminate

the need for a drain tank.

When the water collects to level (A) in the

pump reservoir, the condensate pump

begins to operate and discharge the water.

When the water level drops below level

(B), the condensate pump stops.

Note: If for any reason the water level

exceeds that of level (A) in the pump reservoir, an overflow drain switch stops the

compressor operation, and the LCD displays "AS".
Note: If the fan mode control DIP switch (see page 24) is set to the ST
OP position,

the entire unit (including fan operation) turns off due to the over flow drain switch.

DISCHARGE HOSE

CONDENSATE

PUMP

RESERVOIR

CONDENSATE PUMP