Finishing Around the Fireplace

Combustible mantels and mouldings may be safely installed over the
top and on the front of the fireplace provided that they do not project
beyond shaded area shown in Figure 19a. Side wall clearances are
3". Combustible surrounds may be installed with 3" clearance to the
side of the fireplace as shown in Figure 19b.

Fireplace Facing

When selecting the finish material for your fireplace, it is important to
remember the following: BRASS TRIMS MUST NOT BE
OBSTRUCTED IN ANY WAY - to do so restricts the air supply for
the control compartments and heat exchanger it also prevents
access for servicing controls.

The face of the fireplace may be painted to match the room decor,
provided you use a heat-resistant paint. Decorative facing must not
extend past the fireplace opening at all, because it will interfere with
the access to retainers for removal of glass door.

Installation

We recommend careful consideration be given to the effects of
elevated mantel temperatures which may be in excess of product
design, for example: candles, plastic or pictures. This can cause
melting, deformation, discoloration or premature failure of T.V. and
radio components.

Figure 19b.

Combustible surrounds.

Sheetrock/

Drywall

Header

3

45°

Painting:

Special care is recommended by the Master Painters and Decorators
Association, when painting the fireplace surrounds, to select and
apply a quality Alkyd sealer prior to the applying of latex paints. This
is to prevent leaching of water from evaporation and causing a
brownish staining effect to paint over coats.

Figure 19a. Combustible mantles and facings.

Mantels & Surrounds

NOTE: National Canadian Gas Association mantel test requirements
are for fire hazard prevention to combustible materials.

New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
fireplaces which are hot, fuel and energy efficient.

Please be aware; temperatures over the mantel will rise above
normal room temperature and walls above fireplace may be hot to
touch.

Top of fireplace

Combustible Facing

Combustible construction
allowed in shaded area.

1

2

3

4

5

6

7

8

9

10

11

12

Wiring

Gas Control and Pilot Wiring

MW38-DV-I

Honeywell (Q3450)
Pilot Assembly

Pilot Electrical

Harness Connector

Honeywell Gas
Control (SV9501M)

Gas Control

Connector

Fuse

Limit
Switch

Wall

Switch

Fan Plug
Receptacle

Junction Box

Junction Box Cover

White

Black

Green

40 VA
Transformer

115VAC

24VAC

Grnd Screw

Figure 20. Wiring for the MW38-DV-I with Honeywell gas control and

pilot.