Section 3-3-3: heat shields, Installation – Montigo H38DF PRC User Manual
Page 18
H*38DF PRC Panorama Indoor Gas Fireplace
Page 18
XG0211 - 150204.1
Installation
Note: Images are shown without screens for clarity purposes. However,
your fireplace should not be operated without proper installation of
screens.
Section 3-3-3: Heat Shields
Installing a Wall Mounted RHS8 Heat shield
The RHS8 Heat shield CANNOT be used when the Termination is WITHIN
36" Min. horizontal and 60" Min. vertical from the fireplace, or directly
off the rear of the fireplace, as shown figure 16a. The RHS101 Heat
Shield (Figure 17 and 17a) MUST be used within the noted dimensions.
To install the RHS8, frame an opening in combustible construction,
Figure 16 below. Slide the Heat shield in place over the vent pipe
which attaches to the fireplace. After the fireplace and vent pipe has
been installed, clearances should match the dimensions in Figure 16.
Figure 17. RHS101 Installation. (Install by sliding Outer Section over vent pipe
where it passes through the combustible construction.
Figure 17a. Heat Shield. After sliding the outer section in place.
Termination
Drywall / sheetrock
RHS101 Heat Shield, inner Section
RHS101 Heat Shield
Outer Section
Installing a Wall Mounted RHS101 Heat shield.
The RHS101 Heat shield MUST be used where the RHS8 Termination
(Figure 16 and 16a) CANNOT be used. Use the RHS101 where any
of the dimensions are within the parameters shown, figure 16a.
To install the RHS101, Slide the Inner Section over the vent pipe that
will connect to the fireplace. Then fasten the vent pipe to the back of the
fireplace with a minimum of three sheet metal screws. From the outside
slide the RHS101 outer section on see Figure 17. To complete the
installation fasten the Heat Shield Outer Section & Termination frame
to the structure Figure 17a.
Combustible
framing
Termination
Drywall / sheetrock
RHS101 Heat Shield, inner Section
RHS101 Heat Shield
Outer Section
Vent pipe, from fireplace
RHS8 Heat Shield
1” Min. Both sides Typical
1” Min.
1” Min.
Combustible Framing
Figure 17b.
RHS101 Installation.
Outer Shield 10 1/4”
3/8” Min. Both sides Typical
3/8” Min.
3/8” Min .
Combustible Framing
12” x 12”
Inner Shield 9 3/8”
Figure 16.
RHS8 Installation. (Install by sliding over vent pipe where it passes
through the combustible construction).
Figure 16a.
RHS8 Installation. (Minimum requirements).
RHS8 Heat
Shield
36” Min
60” Min.