Monster HTUPS 3700 User Manual
Page 44
36
For example:
OF3
note:
a . Master/Slave slide switch is enabled:
The bank-0 outlet is master outlet . The slave outlets ( bank-1 and bank-2 ) turn on or off, they will depend on
the master outlet output power . If the master outlet output power over 45W, the slave outlets will be turned
on . If the master outlet output less than 25W, the slave outlets will be turned off .
The master outlet will be turned on after 8 seconds when UPS is plugged into utility power .
UPS will not accept the “OF0
send these commands to UPS .
The “OF6
b . Master/Slave slide switch is disabled:
The bank-0, bank-1 and bank-2 outlets are defined to unswitched outlets . The unswitched outlets will
be turned on after 8 seconds when UPS is plugged into utility power . The monitor software can send the
“OF0
bank-1, bank-2, bank-3, bank-4 and bank-5 outlets .
The “OF6
RS-232 COMMUnICaTIOnS PROTOCOl anD COMManD SeT
COn’T