beautypg.com

2 divert decision logic – K-Patents DD-23 User Manual

Page 30

background image

26

7.2 Divert decision logic

After the system has evaluated the solid contents to be either safe or unsafe (see Sec-
tion 7.1), it decides whether the the system should be in the DIVERT state. This deci-
sion is made according to the 󰅮low diagram in Figure 7.2.

The default state of the system is the DIVERT state. It can be changed to the NO DIVERT
state only by manually pressing the

DIVERT RESET

push-button when the solid content

is suf󰅮icient (SAFE SOLIDS). If the solid content drops to UNSAFE, the system drops
into the DIVERT state.

The only exception to this is when the HEADER WASH is active. In that case the solid
content checking is skipped. The system may then be switched between the DIVERT
and NO DIVERT states by using the

EMERGENCY DIVERT

and

DIVERT RESET

push buttons

in the operator panel (or the equivalent external emergency divert and divert reset
buttons).

The system will drop to the DIVERT state in all cases when the

EMERGENCY DIVERT

button (or its external counterpart) is pressed.

NO DIVERT

DIVERT

HEADER WASH

active?

Divert from

safe solids logic?

EMERGENCY

DIVERT

pressed?

DIVERT RESET

pressed?

yes

no

yes

no

yes

no

no

yes

Figure 7.2

The divert decision logics