4.2 Divert control unit DD-23 startup

For the refractometer startup, consult Chapter 5 in the separate Process refractometer
PR-23 manual.

1. Check the wiring and supply voltage.

Before the power is switched on, the divert output relay ’normal operation’ is in
divert position.

2. Connect the mains power to start the system.

There are no power switches in the instruments. They are always On when the
mains power is connected.

3. While the Control unit is powering up, the

DIVERT

and

SOLIDS ALARM

lights are both

blinking. When the unit is fully functional, it is in the divert mode: the

DIVERT

light

is on and the

SOLIDS ALARM

light is blinking.

4. Press the

LIGHT TEST

button on the Divert control unit. All 12 lights should switch

on.

5. Reset the solids alarm by pressing the

ALARM RESET

button.

The indicator stops blinking and should stay on.

6. Each indicating transmitter should now state refractometer letter, either a or b, in

the upper left corner of the transmitter display. If there’s a question mark instead
of a letter on either of the transmitters, see Chapter 6.
If the process pipe is full, the message for each refractometer should be

NORMAL

OPERATION

; if process pipe is still empty, message will be

NO SAMPLE

.

Now activate refractometer A into the Divert by pushing the button

A IN OPERATION

on the Divert control unit panel. The button lights up and on the transmitter dis-
play the refractometer letter changes to capital A. Then activate refractometer B
similarly by pushing the button

B IN OPERATION

.

If the green

IN OPERATION

light blinks, the refractometer in question is perform-

ing wash. The refractometer will automatically come into operation after it has
󰅮inished washing.

7. Now the Divert control system DD-23 is set for normal monitoring operation.

8. When black liquor is in the line, check that the prism wash is working for each

refractometer. First press soft key

MENU

on the transmitter keyboard, then choose

3 SYSTEM STATUS

to get to the system status display. Now press soft key

WASH

to

initiate manual wash; follow the optical image and check that it changes during
the steam wash. If wash was successful, wait until message is

NORMAL OPERATION

and then proceed with startup. If wash doesn’t seem to work, see Chapter 6.

9. If the three green lights on the third row are all on and all conditions for safe boiler

operation are satis󰅮ied, turn off diversion by pressing the

DIVERT RESET

button. All

warning lights are now turned off and only the 3 green lights are on.