2 divert control unit dd-23 startup – K-Patents DD-23 User Manual
Page 18

14
4.2 Divert control unit DD-23 startup
For the refractometer startup, consult Chapter 5 in the separate Process refractometer
PR-23 manual.
1. Check the wiring and supply voltage.
Before the power is switched on, the divert output relay ’normal operation’ is in
divert position.
2. Connect the mains power to start the system.
There are no power switches in the instruments. They are always On when the
mains power is connected.
3. While the Control unit is powering up, the
DIVERT
and
SOLIDS ALARM
lights are both
blinking. When the unit is fully functional, it is in the divert mode: the
DIVERT
light
is on and the
SOLIDS ALARM
light is blinking.
4. Press the
LIGHT TEST
button on the Divert control unit. All 12 lights should switch
on.
5. Reset the solids alarm by pressing the
ALARM RESET
button.
The indicator stops blinking and should stay on.
6. Each indicating transmitter should now state refractometer letter, either a or b, in
the upper left corner of the transmitter display. If there’s a question mark instead
of a letter on either of the transmitters, see Chapter 6.
If the process pipe is full, the message for each refractometer should be
NORMAL
OPERATION
; if process pipe is still empty, message will be
NO SAMPLE
.
Now activate refractometer A into the Divert by pushing the button
A IN OPERATION
on the Divert control unit panel. The button lights up and on the transmitter dis-
play the refractometer letter changes to capital A. Then activate refractometer B
similarly by pushing the button
B IN OPERATION
.
If the green
IN OPERATION
light blinks, the refractometer in question is perform-
ing wash. The refractometer will automatically come into operation after it has
inished washing.
7. Now the Divert control system DD-23 is set for normal monitoring operation.
8. When black liquor is in the line, check that the prism wash is working for each
refractometer. First press soft key
MENU
on the transmitter keyboard, then choose
3 SYSTEM STATUS
to get to the system status display. Now press soft key
WASH
to
initiate manual wash; follow the optical image and check that it changes during
the steam wash. If wash was successful, wait until message is
NORMAL OPERATION
and then proceed with startup. If wash doesn’t seem to work, see Chapter 6.
9. If the three green lights on the third row are all on and all conditions for safe boiler
operation are satisied, turn off diversion by pressing the
DIVERT RESET
button. All
warning lights are now turned off and only the 3 green lights are on.