beautypg.com

2 general view of the machine, 3 distribution network – Kemppi MinarcTig 250MLP User Manual

Page 8

background image

EN

8

2.2

general view of the machine

1.

2.

3.

5.

4.

1.

Welding torch

2.

Earthing cable and earthing clamp

3.

Main switch

4.

Mains cable (MinarcTig 180 in the picture)

5.

Shielding gas hose connector

2.3

Distribution network

All regular electrical devices without special circuits generate harmonic

currents into distribution network. High rates of harmonic current may cause

losses and disturbance to some equipment.

minarctig 180, 180mlp:

WARNING: This equipment does not comply with IEC 61000-3-12. If it is

connected to a public low voltage system, it is the responsibility of the

installer or user of the equipment to ensure, by consultation with the

distribution network operator if necessary, that the equipment may be

connected.

minarctig 250, 250mlp:

This equipment complies with IEC 61000-3-12 provided that the short-circuit

power S

sc

is greater than or equal to 1.5 MVA at the interface point between

the user's supply and the public supply network. It is the responsibility of

the installer or user of the equipment to ensure, by consultation with the

distribution network operator if necessary, that the equipment is connected

only to a supply with a short-circuit power S

sc

greater than or equal to

1.5 MVA.

8

MinarcTig 180, 180MLP, 250, 250 MLP

This manual is related to the following products: