PD-01 PROFIBUS-DP Module

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

26

Item Name Type

Description

Default

3 Data Input 3

UINT This is a MODBUS address. The 3rd word in

PZD of cyclic output data will be sent to this
address if select Module = "4 PKW, 4 PZD".

0x0000

4 Data Input 4

UINT This is a MODBUS address. The 4th word in

PZD of cyclic output data will be sent to this
address if select Module = "4 PKW, 4 PZD".

0x0000

5 Data Output 1

UINT This is a MODBUS address. PD-01 will

monitor this address, and copy the return
data to the 1st word in PZD of cyclic input
data.

0x2101

6 Data Output 2

UINT This is a MODBUS address. PD-01 will

monitor this address, and copy the return
data to the 2nd word in PZD of cyclic input
data.

0x2102

7 Data Output 3

UINT This is a MODBUS address. PD-01 will

monitor this address, and copy the return
data to the 3rd word in PZD of cyclic input
data if select Module = "4 PKW, 4 PZD".

0x2103

8 Data Output 4

UINT This is a MODBUS address. PD-01 will

monitor this address, and copy the return
data to the 4th word in PZD of cyclic input
data if select Module = "4 PKW, 4 PZD".

0x2104

9 d_state

UINT

This is a flag. If address in Data Output 1 ~
Data Output 4 is continuous, set it to 1, and
set the others to 0.

0x0001

10 din_len

UINT This is a length, and unit is word. It specifies

the length of PD-01 to process data in PZD, if
user select the Module = "4 PKW, 4 PZD", but
din_len is 3, PD-01 will process 3 word and
ignore the 4th word.

0x0002

11 dout_len

UINT This is a length, and unit is word. It specifies

the length of PD-01 to monitor data from AC
Drive, if user select Module = "4 PKW, 4
PZD", but dout_len is 3, PD-01 will monitor 3
word and ignore the 4th address.

0x0002

12 LossDPComTreat UINT This variable indicates that the PD-01 will

take action when communication with
Profibus network is lost, the value can be
assigned as follows:
00 – Ignore event and continue;
01 – Stop according to Pr “Stop Method” in

VFD series Drives.

0x0001