Response time about pd-01 – Delta PROFIBUS-DP Module for VFD Series Drives PD-01 User Manual

Page 22

background image

PD-01 PROFIBUS-DP Module

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

19

Request

Response

Word 1 (PKE)

17A0

Word 1 (PKE)

17A0

Word 2 (IND)

7000

Word 2 (IND)

7000

Word 3 (PWE1)

0000

Word 3 (PWE1)

0000

Word 4 (PWE2)

0000

Word 4 (PWE2)

0300

If PD-01 returns the data 0x0300, it indicates that Scan port is disconnected. Please
refer to Section 6.2 for details.

Example 5: Access error
If take any action using PKW to access parameter in AC Drives and it fails, PD-01 will
response error information. Suppose that Master send data sequence is 202D 8000
0000 0002, if VFD series Drives does not find this address (0x07FD), it will respond
the data sequence 702D 8000 0000 0000, response ID is 7 which means cannot
process request (with error number), and error number is 0 (Illegal Parameter
Number).

Request

Response

Word 1 (PKE)

202D

Word 1 (PKE)

702D

Word 2 (IND)

8000

Word 2 (IND)

8000

Word 3 (PWE1) 0000

Word 3 (PWE1)

0000

Word 4 (PWE2) 0002

Word 4 (PWE2)

0000

Response time about PD-01

The update time via PROFIBUS connection can be divided in 3 parts:

T1: Communication time in transmit data from the master to PD-01, and

T2: Wait processing in data buffer of PD-01, and

T3: Communication time in transmit data from PD-01 to VFD Drives.

T1

T3

Master

Data Buffer

Timer

PD-01

VFD

series

Drives

T2