Herrmersion re, Installation check list – Herrmidifier Herrmersion RE User Manual
Page 9

Herrmersion RE
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
9
www.herrmidifier-hvac.com
4"
RECOMMENDED
8"
RECOMMENDED
POWER SUPPLY:
1. MATCHES DATA PLATE
2. IS PROPERLY GROUNDED
3. CAN CARRY AT LEAST 125%
OF RATE AMP DRAW
4. DISCONNECT SUPPLIED BY
OTHERS.
MAKE SURE ALL HIGH VOLTAGE
ELECTRICAL CONNECTIONS
ARE TIGHT.
NO UNTRAPPED LOW SPOTS
IN STEAM SUPPLY.
AIR FLOW IS HORIZONTAL OR VERTICAL UPFLOW
*A SPECIAL PIPE IS REQUIRED FOR VERTICAL DOWNFLOW,
OR A VERTICAL DISTRIBUTOR PIPE IN A HORIZONTAL
AIR FLOW.
MAKE SURE ALL HIGH VOLTAGE
ELECTRICAL CONNECTIONS ON
STEAM CYLINDER ARE TIGHT
(15-20 in/lbs)
3/4" MIN. I.D./1" MAX O.D.
FLEXIBLE DRAIN CONNECTION
DURING FILL CYCLE CHECK TO SEE IF ANY
WATER IS DRAINING FROM UNIT. A LOT OF
WATER FLOWING OUT OF THE UNIT WOULD
INDICATE EXCESSIVE WATER PRESSURE.
REDUCE THROUGH METERING FILL SOLENOID
OR SUPPLY VALVE TO HUMIDIFIER. A SMALL
AMOUNT OF WATER IS NOT UNCOMMON.
6" MIN. LENGTH OF 1-1/4" MIN. I.D. COPPER LINE.
IF PVC IS USED, LOCAL CODES REQUIRE A LOWER
TEMPERATURE DRAIN WATER IS NOT UNCOMMON.
BALANCE OF DRAIN LINE TO BE 1" MIN. I.D.
WITH A MINIMUM PITCH OF 1/8" PER 12" OF RUN
ENSURE OVERFLOW PIPING IS INSTALLED
AND TIGHT IF USING RAW WATER. A 5-6” P-TRAP IS
REQUIRED TO ENSURE STEAM DOES NOT ENSUE
FROM THE OVERFLOW PIPING. OVERFLOW
IS NOT REQUIRED WITH DI/RO WATER. SKIMMING
MUST BE DISABLED IN THE CONTROL SETTINGS.