Unavoidable Low Spot or Sagging Vapor Hose

EST-250

CONDENSATE

TRAP

1/2"

TUBE
TO

DRAIN

AT LOWEST

POSSIBLE

POINT

If any low spots are present in the vapor line or the unit is

mounted higher than the dispersion system, a condensate

trap must be mounted at the lowest point in the line. This will

act to remove any pooled condensate from the steam line

and prevent spitting in the duct.

ELECTRICAL

WARNING

Open all disconnect switches before installing the unit.

Failure to do so could result in personal injury or death from

electrical shock.
Ensure that adequate service is available to carry 125% of

the rated unit amperage. Field wiring of the main power

supply is connected directly to the main power contactor

located inside the right side electrical compartment. Please

refer to the wiring diagram appropriate for the model

Herrmersion you have. A separate grounding lug is provided

for the ground wire. This is also located inside the right side

electrical compartment. Install short circuit & over-current

protection in accordance with the National Electric Code,

State, and local electrical codes.

Model Capacity/Amperage Table

Unit Model

Max.

Capacity

Voltage/

Phase

Qty.

Elements

Total

Amps

RES_-240-1-30

30 lb/hr

240/1

2

41.7

RES_-480-1-30

30 lb/hr

480/1

2

20.8

RES_-208-3-45

45 lb/hr

208/3

3

41.6

RES_-240-3-45

45 lb/hr

240/3

3

36.1

RES_-480-3-45

45 lb/hr

480/3

3

18.0

RES_-600-3-45

45 lb/hr

600/3

3

14.4

RES_-480-3-90

90 lb/hr

480/3

6

36.1

RES_-600-3-90

90 lb/hr

600/3

6

28.9

A wiring diagram is located inside the control cabinet. The

wiring between the control cabinet and the humidifier unit

must be 105 °C rated wire. Use copper conductors only.

Please refer to the Control section in this manual for

information regarding electrical connections to be made

directly to the control system.

NOTE: Only qualified electrical personnel should perform

installation and start-up procedures.

WARNING

Open all disconnect switches before installing the unit.

Failure to do so could result in personal injury or death from

electrical shock.

The following pages contain unit wiring diagrams. Please

identify the applicable wiring diagram primarily by the number

of heating elements present on your unit. Refer to the chart

above. Units designed for 30 lbs/hr of steam output will have

2 heating elements, units designed for 45 lbs/hr of steam

output will have 3 heating elements and units designed for

90 lbs/hr of steam output will have 6 heating elements. The

only other difference between these diagrams pertains to the

control transformer. Please identify the appropriate wiring

diagram for your unit on the following pages.