Herrmersion re – Herrmidifier Herrmersion RE User Manual
Page 7

Herrmersion RE
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
7
www.herrmidifier-hvac.com
Standard Duct Distribution
STEAM DISCHARGE MUST ALWAYS
BE FROM THE TOP OF DISTRIBUTOR
VERTICAL DUCT
HORIZONTAL DUCT
NO SAGS
ALLOWED
MIN. 8% (1" PER FOOT)
10" MIN.
(254mm)
The rubber vapor hose carries the steam to the dispersion
tube and condensate back to the unit tank. It must have an
8% (1” per foot) pitch back to the unit. Support the vapor
hose so that it maintains proper pitch when the unit is in
operation.
Single Distribution Tube
DUCT HEIGHT
10" - 16"
(254MM) - (406MM)
DUCT HEIGHT > 16"
(406mm)
(76mm)
h =
H
2
-5" (127mm)
h
3"
H
Units up to 45 pounds per hour of steam will use one steam
distribution tube. Refer to the diagram above for mounting
location.
Dual Distribution Tubes
h (in)=6+
(H-15)
2
(76mm)
DUCT HEIGHT > 16"
(406mm)
AIR
FLOW
DUCT HEIGHT
10" - 16"
(254MM) - (406MM)
3.00" (76mm)
6.5" (165mm)
8.00
(203mm)
3"
h
H
Units above 45 pounds per hour of steam will use two duct
dispersion tubes. Refer to the diagram above for mounting
location.
Single to Dual Duct Distribution
EST-255
"Y" CONNECTOR
If you must split the discharge of one steam outlet into two
ducts with the same static pressure, a “Y” connector is
available from the factory. The length of vapor hose after
the “Y” connector must be the same to ensure equal steam
distribution.