Control Module Specifications:

Power

24 Vac ± 10%, 50-60 Hz, 18 VA power consumption (24 VA with Bacview attached), 26 Vdc (25 V

min, 30 V max), Single Class 2 source only, 100 VA or less

Physical

Rugged GE C2950 Cycoloy plastic

Operating Range

-0° to 130°F (-18.5° to 54.4°C); 10 to 90% relative humidity, non-condensing

Digital Outputs

5 digital outputs, relay contacts rated at 1 A resistive @ 24 Vac, configured as dry contact, normally

open

Analog Outputs

3 analog outputs, rated as 0-10Vdc, 5mA (max). 8 bit D/A resolution

Universal Inputs

8 universal inputs. Inputs 1-6 configurable as thermistor or dry contact; inputs 1 and 2 also configu-

rable as 0-5 Vdc type inputs; inputs 7 and 8 are reserved to use with 1k-10 koHm adjustment potenti-

ometers. Resolution of 10 bit A/D.

Communication

Ports

Port 1: Jumper configurable for ARCNET or EIA-485 communication. In ARCNET mode, the port

speaks BACnet (at 156k bps). In EIA-485 mode, the communication protocol and baud rate desired

are DIP switch selectable between BACnet MS/TP, Modbus RTU, or N2. Rnet port: Interface with a

BACview5, BACview6 , RS sensors, or local laptop

Optional Card Port LonWorks Option Card for connection to Free Topology LON networks (TP/FT-10 Channel)
Status Indication

Visual (LED) status of serial communication, running, errors, power, and all digital outputs

Battery

Battery CR123A has a life of 10 years with 720 hours of cumulative power outage

Protection

Built-in surge transient protection circuitry. Module protected by internal solid state Polyswitches on

incoming power and network connections. Polyswitches do not need to be replaced as they will reset

themselves once the condition that caused them to “trip” returns to normal.

Listed by

FCC Part 15 - Subpart B - Class A. Pending listings at the time of publishing this document: UL 916

(PAZX), cUL C22.2 No. 205-M1983 (PAZX7), CE (1997).

BTL (BACnet Test Labs) - BACnet Advanced Application Controller (B-AAC) http://www.bacnetinter-

national.net/btl/index.php?m=47

Display Module Specifications:

Power

Supplied by the 4 conductor cable (+12Vdc @ 250mA).

Physical

Rugged aluminum enclosure for protection and easy backplane mounting.

Operating Range

32° to 130°F (0° to 54.4°C), 10%-90% RH non-condensing.

Backlit LCD

4-line by 40-character display.

Listed by

UL 916 (PAZX), CE (1997), FCC Part 15 - Subpart B - Class A.

Weight

1.2 lbs. (0.54 Kg)

Mounting

Wall or panel mounting; remote mounting up to 500 feet. Standard J box may be used.

Dimensions.

9-5/8” (width) by 4-15/16” (height) by 1” (recommended panel depth)

245mm (width) by 125mm (height) by 25mm (recommended panel depth).