Groth 3011L User Manual
Page 5

4
GENERAL SAFETY INSTRUCTIONS
This section is intended as an overview of safety guidelines that should be followed during the installation, operation and 
maintenance of the Groth model 3011L, & 3041L, 3011H & 3041H, 3011HP & 3041HP Blanket Gas Regulators. To understand 
the context of these warnings and instructions, read and understand this complete manual. 
The blanket gas regulator is one of the principal protection devices typically installed on a product storage tank. It is a precision 
regulator that is designed to maintain a positive pressure on the tank. This will prevent product loss or contamination from 
atmospheric air when pumping liquid out or when the stored fluid cools. 
The blanket gas regulator should not be used as a substitute for a vacuum relief valve. An interruption in the blanket gas supply 
could cause tank failure. 
SAFETY WARNINGS
IN THE EVENT OF AN ACTUATOR OR PISTON DIAPHRAGM FAILURE, THE REGULATOR WILL FAIL IN THE OPEN 
POSITION. GAS FLOW WILL NOT BE SHUT OFF. EMERGENCY AND OR PRESSURE/VACUUM RELIEF VALVES MUST BE 
SIZED TO INCLUDE BLANKET GAS REGULATOR CAPACITY IN ADDITION TO NORMAL AND EMERGENCY VENTING 
REQUIREMENTS. 
IN THE EVENT OF BLANKET GAS SUPPLY FAILURE, THE REGULATOR WILL NOT PROTECT THE TANK FROM AN 
EXCESS VACUUM CONDITION. BLANKET GAS SUPPLY FAILURE SHOULD BE CONSIDERED IN THE SIZING, 
SELECTION AND SETTING OF PRESSURE/VACUUM RELIEF VALVES. 
BLANKET GAS REGULATOR FLOW CAPACITY IS BASED ON A KNOWN SUPPLY PRESSURE AND A PROPERLY SIZED 
GAS DISTRIBUTION SYSTEM. 
ALL SUPPLY PIPING MUST BE FREE OF WELD SLAG AND OTHER DEBRIS BEFORE INSTALLING THE BLANKET GAS 
REGULATOR. IF WELD SLAG OR DEBRIS FLOWS THROUGH THE REGULATOR THERE IS A HIGH POTENTIAL FOR 
SEATING SURFACE AND O-RING DAMAGE. THIS TYPE OF DAMAGE WILL CAUSE THE REGULATOR TO CONSTANTLY 
FLOW BLANKETING GAS TO THE TANK. TO PREVENT DAMAGE FROM WELD SLAG OR DEBRIS CONSIDER 
INSTALLING AN UPSTREAM FILTER OR STRAINER. AN ENGINEERING ANALYSIS MUST BE PERFORMED TO 
EVALUATE THE EFFECT THESE DEVICES MAY HAVE ON THE BLANKET GAS REGULATOR FLOW CAPACITY. 
THE REGULATOR IS NORMALLY FACTORY SET AT THE DESIRED SET PRESSURE. THE SPRING RANGE IS STAMPED 
ON THE NAMEPLATE. DO NOT ATTEMPT TO RE-ADJUST THE SET PRESSURE BEYOND THE LIMITS SPECIFIED IN 
TABLE 3. 
THE REGULATOR IS TO BE CONNECTED TO THE TANK OR VESSEL WITH A MINIMUM 0.31" ID TUBING SENSE LINE. 
THIS LINE MUST BE KEPT OPEN AND UNOBSTRUCTED TO ENSURE THAT THE REGULATOR SENSES THE ACTUAL 
TANK PRESSURE. LONG SENSE LINES MAY REQUIRE A LARGER DIAMETER AND CARE MUST BE TAKEN TO ASSURE 
THAT THE LINE IS SELF-DRAINING. FOR SOME APPLICATIONS, A NITROGEN PURGE MAY BE REQUIRED TO ENSURE 
THAT THIS LINE REMAINS OPEN. CONSULT FACTORY FOR RECOMMENDATIONS. 
DO NOT ATTEMPT TO REMOVE THE REGULATOR FROM THE LINE OR PERFORM FIELD REPAIRS IN LINE WITHOUT 
FIRST ISOLATING THE REGULATOR FROM BOTH THE TANK AND THE SUPPLY GAS LINE. BLEED ALL PRESSURE 
BEFORE REMOVING THE SPRING BONNET OR THE FLOW ORIFICE LOCKING SCREW, OR OPENING UP THE 
ACTUATOR HOUSINGS. 
NOTE THE ORIFICE SLEEVE POSITION WHEN DISASSEMBLING THE REGULATOR. IT WAS FACTORY SET ACCORDING 
TO THE FLOW REQUIREMENTS LISTED ON THE ORDER AND MUST BE RE-INSTALLED IN THE SAME POSITION TO 
ENSURE THE CORRECT FLOW. 
THE REGULATOR BODY AND ACTUATOR HOUSING ARE EXPOSED TO PROCESS VAPORS. OBSERVE ALL SAFETY 
PRECAUTIONS AS SPECIFIED ON THE MATERIAL SAFETY DATA SHEET FOR THE PRODUCTS THAT ARE IN THE TANK. 
THE VENTS ON THE SPRING BONNET AND ACTUATOR HOUSING MUST BE CLEAN AND OPEN TO THE ATMOSPHERE 
AND SHOULD BE INSPECTED PERIODICALLY. 
THE RECOMMENDED SET PRESSURE RANGE OF THE REGULATOR SPRING IS STAMPED ON THE NAMEPLATE. 
NEVER ADJUST A SPRING FOR A SET PRESSURE BEYOND ITS DESIGN RANGE AS SPECIFIED IN TABLE 3. 
EXCEEDING THE SPRING UPPER LIMIT MAY COMPRESS THE SPRING TO ITS SOLID HEIGHT, AND PREVENT THE 
REGULATOR FROM CLOSING. SETTING IT BELOW THE LOWER LIMIT MAY PREVENT THE REGULATOR FROM 
OPENING FULLY AT THE REQUIRED PRESSURE. 