Table 4 – flow capacity setting, Table 5 – orifice sleeve position, Blanketing the tank – Groth 3011L User Manual
Page 10

9
TABLE 4 – FLOW CAPACITY SETTING
Table 4 shows flow capacity for a regulator set at 100% full open. Unless otherwise specified, the orifice selector sleeve [12] is
factory set at the 100% full open position.
* Orifice sleeve installed in 100% flow capacity position.
NOTE: Flow capacity values are in SCFH. For NCMH, multiply the listed capacities by 0.029
If reduced capacity is specified on an order, the sleeve is set at the appropriate restriction. Actual capacity at any other position
can be calculated by multiplying the capacity value from Table 4 for a specific pressure by the decimal value from Table 5.
TABLE 5 – ORIFICE SLEEVE POSITION
ORIFICE SLEEVE POSITION
1 2 3 4 5 6 7 8
1.0 0.75 0.50 0.25 0.20 0.15 0.10 0.05
FLOW CAPACITY MULTIPLIER
1/2" Models are only available with positions 1, 2, 3, and 4
BLANKETING THE TANK
Before installing a new or replacement regulator, the tank pressure must be below the desired set pressure so the regulator setting
can be verified. Sequentially open the block valves in the following order: (1) Sense Line, (2) Regulator Discharge Line and (3)
Regulator Supply (See Figure 3).
If the regulator was set at the factory, blanket gas will begin to flow immediately. The tank pressure must be monitored closely to
verify that the gas flow shuts off at the set pressure.
If the regulator was not set at the factory, make sure that the adjusting screw [11] is backed out as far as possible (no spring
compression). When the blanket gas supply valve is turned on, there will be no flow, unless the tank pressure is very low. Now
slowly turn the adjusting screw to increase tank pressure and the gas will begin to flow. The tank pressure can be increased as
gradually as desired until the correct pressure setting is attained. When tank pressure is reached, back out adjusting screw, if
necessary, until gas flow stops.
WARNING: In the event of an actuator diaphragm [42] or piston diaphragm [36] failure, the regulator will fail in the open
position. Gas flow will NOT be shut off. Emergency and or pressure/vacuum relief valves must be sized to include
blanket gas regulator capacity in addition to normal and emergency venting requirements.
PSIG
BARG
1/2"
1"
1/2"
1"
1/2"
1"
1/2"
1"
5
0.34
2160
4600
2810
5800
3660
7400
2800
5700
10
0.69
3250
7100
4230
8800
5490
11300
4190
8700
15
1.03
4370
9200
5690
11500
7390
14600
5630
11300
20
1.38
5130
11200
6680
14000
8680
17900
6610
13800
30
2.07
6630
15100
8630
18900
11210
24000
8540
18600
40
2.76
8140
18800
10590
23600
13760
30000
10480
23200
50
3.45
9650
22500
12560
28200
16320
35800
12430
27700
60
4.14
11160
26000
14520
32600
18860
41500
14370
32100
80
5.52
14180
33000
18440
41300
23950
52600
18250
40700
100
6.89
17200
40000
22370
50100
29060
63700
22140
49300
120
8.27
20210
47000
26290
58800
34150
74800
26020
57900
140
9.65
23230
53900
30220
67500
39250
85900
29910
66500
160
11
26240
60900
34140
76300
44340
97000
33790
75100
180
12.4
29260
67900
38060
85000
49440
108100
37680
83700
200
13.8
32280
74900
41990
93700
54540
119200
41560
92300
FLOW CAPACITY (SCFH) *
Supply Pressure
AIR
Carbon Dioxide
Nitrogen
Natural Gas 0.55 S.G.