Water wash control panel - model ww, W / vacuum breaker, Detail of label & switches – Greenheck Waterwash (458292) User Manual

Page 39: Model description, Pipe size

background image

39

April 2005

®

1 = 1 WASH SEQUENCE

5 = 5 WASH SEQUENCES

4 = 4 WASH SEQUENCES

3 = 3 WASH SEQUENCES

2 = 2 WASH SEQUENCES

7 = 3/4" PIPE
10 = 1" PIPE

WW

-

-

A = 24 HOUR TIMER

MODEL DESCRIPTION

WATER WASH CONTROL PANEL - MODEL WW

OR SEQUENCE OF HOOD

LENGTH OF LONGEST HOOD

LONGEST LENGTH OF HOOD WASHED AT ONE TIME

WASH OPTION. PIPE SIZE WILL DEPEND ON THE

HOOD LENGTH > 20' MUST USE THE SEQUENCE

PIPE SIZE

1"

3/4"

>10' - 20'

4' - 10'

PIPE SIZE

W / VACUUM BREAKER

LOW DETERGENT INDICATOR

SEQUENCED HOODS

TIMER

24 HOUR

OPTIONAL:

7 DAY

B = 7 DAY TIMER

DOOR

HINGED

HINGED

DOOR

9.53

18.91

DETERGENT

LINE

PIPE CONNECTION

CONNECTIONS

ELECTRICAL

3.50

2.00

8.37

6.37

4.37

2.37

12.56

3.50

30"

9"

30"

FIRE MODE

LOW DETERGENT

KITCHEN VENTILATION SYSTEMS

WATER WASH HOOD CONTROL PANEL

DETAIL OF LABEL & SWITCHES

INDICATOR

LIGHT

START FAN

LIGHTED

PUSH-

BUTTON
SWITCH

OPTIONAL

INDICATOR

LIGHT

HOOD LIGHTS

PUSH-

BUTTON
SWITCH

LIGHTED

LIGHTED

PUSH-

BUTTON
SWITCH

1. PUSH THE START FAN SWITCH BEFORE TURNING ON THE COOKING EQUIPMENT.

2. WHEN THE COOKING EQUIPMENT HAS BEEN SHUT DOWN AND ALLOWED TO

COOL PROPERLY, PUSH THE STOP FAN / START WASH SWITCH. THIS WILL

STOP FAN /
START WASH

OPERATING INSTRUCTIONS

P.N. 454034

OPERATION.

FIRE MODE IS INITIATED BY AN EXTERNAL SIGNAL FROM A FIRE

SUPPRESSION SYSTEM. IN FIRE MODE THE WATER WASH SYSTEM WILL TURN

ON THE EXHAUST FAN AND CONTINUOUSLY SPRAY WATER INTO THE HOOD.

THE 24 HOUR TIMER OPTION THE WASH CYCLE WILL BEGIN AT THE SET

TIME. AFTER THE WASH CYCLE THE SYSTEM WILL RESET FOR THE NEXT

SEE THE INSTALLATION AND OPERATION MANUAL FOR MORE INFORMATION.

FIRE MODE

TURN OFF THE FANS AND START THE WASH CYCLE. IF THE SYSTEM HAS

1"

SEQUENCE OF OPERATIONS

15 SEC. COLD WATER PURGE (OPTIONAL 30 SEC.)
4 MIN. WASH (OPTIONAL 0 TO 10 MIN.)
30 SEC. DETERGENT PURGE (OPTIONAL 1 MIN.)
15 MIN. SEQUENCE DELAY (OPT. 0 TO 45 MIN.)
1 MIN. DRAIN DOWN (OPTIONAL 10 MIN.)
1 MIN. DRY (FANS ON) (OPTIONAL 10 MIN.)

WATER REQUIREMENTS

WATER TEMPERATURE 140° F. TO 180° F
WATER PRESSURE = 40 PSI TO 60 PSI
AVE. WATER USAGE = 1.1 GPM PER LN. FT. OF HOOD

(1.75 DIA. HOLE)

(.88 DIA. HLS)

6.0

CHECK VALVE
FIELD INSTALLED

TO HOOD(S)

DETERGENT PUMP

SHOCK ARRESTOR

SOLENOID VALVE

UNION

PIPE BY OTHERS

PIPE BY OTHERS

UNION

GATE VALVE

WATER TEMPERATURE

& PRESSURE GAUGE

DETERGENT TANK
2.5 GAL. CAPACITY

WATER INLET

OPTIONAL

SEQUENCING V

A

L

V

ES

FIELD INST

ALLED

OPTIONAL

VACUUM BREAKER

FIELD INSTALLED

(@ 40 PSI)