beautypg.com

Controller menu screens – Greenheck Vektor Laboratory Exhaust with VGN Technology Electrical Controls Information (476072) User Manual

Page 21

background image

Controller Menu Screens

The following value ranges are specific to the Air Flow menu screen.

Flow Active reading calculated by the Sure-Aire system.

English = CFM; Metric = m

3

/hr

Flow VDC Scaled voltage output specific to the flow scale.

0 VDC = no flow; 10 VDC = maximum flow

Flow Scale Flow range specific to VGN fan.

English = CFM; Metric = m

3

/hr.

Nozzle Open Active reading stating the % open of the VGN nozzle.

0% = nozzle closed; 100% = nozzle open

The values in this menu are not user-editable and are locked by the controller program.

GREENHECK VGN

AIR

FLOW

FLOW

xxxxx

FLOW VDC X.X VDC

LOW SCALE 0 TO XXXXX

NOZZLE

OPEN

XXX

%

The nozzle controller consists of five menu screens to operate the VGN system. The following information describes
the menu screens in detail.

GREENHECK VGN

SYSTEM

STATUS

FAN

STATUS

XXX

VELOCITY

XXX

FAN

FLOW

XXX

ALARM CONTACT XXX

The following value ranges are specific to the System Status menu screen.

Fan Status Shows the status of the fan.

On or Off

Velocity Determines if outlet velocity is acceptable per system setting.

OK or Low

Fan Flow Determines if fan flow is acceptable per required nozzle area and velocity.

OK or Low

Alarm Contact Alarm and contact closure for the following.

Alarm list:

a. Velocity is below the required preset system value.
b. Fan is shown as running but no flow is being created.

The values in this menu are not user-editable and are locked by the controller program.

GREENHECK VGN

SYSTEM

SETTINGS

H FAN SIZE XX

FLOW

MEASURE

XXXXX

UNITS

XXXXXX

ELEVATION

XXXXX

OUTLET VELOCITY XXXX

The following value ranges are specific to the System Settings menu screen.

H / M / C Fan Size Factory set for system fan size. Selects the correct fan

variables for the control.

Flow Measure Sets the location of the airflow monitor location.

Inlet or outlet condition

Units Sets up the control screen variables for the system.

English or Metric

Elevation Location above sea level the system is located to set air density.

0 to 10,000 feet

Outlet Velocity Required velocity at the VGN Nozzle outlet.

3,000 to 4,000 FPM; 912 to 1216 MPM.

All the values in this menu can be changed by the user. Note factory settings prior to making
adjustments.

GREENHECK VGN

TEST AND BALANCE

T&B

BALANCING

XXX

NOZZLE

%

OPEN XXX

FLOW

CORRECT

XXXX

The following value ranges are specific to the Test and Balance menu screen.

T&B Balancing Used to start the balancing process of the system.

Yes or No.

Nozzle % Open Gives Test and Balance personnel complete control of nozzle

regardless of fan flow.
0% = closed; 100% = open

Flow Correct “K” factor for Test and Balance personnel to measure and adjust

airflow. Note that “K” value is not CFM, but subtracts or adds to
the flow calculation within the program.
-2000 to +2000

All the values in this menu can be changed by the user. Note factory settings prior to making
adjustments.

Electrical Controls Information for Customer-Supplied Variable Frequency Drive

21

VGN Technology

®