background image

Electrical Controls Information for Factory-Supplied Variable Frequency Drive

Wiring Diagram

-

+

0

-

+

1

2

3

5

T1

T2

GND

T3

0

-

+

TRANSDUCER 1

TRANSDUCER 2

1

2

5

3

1

2

3

5

COMM

14

16

AI1

AGND

AO1

1

5

1

2

GND

3

SGND

ISOLATION DAMPER

SURE-AIRE SIGNAL

NOZZLE ACTUATOR 1

OUTGOING POWER - TO FAN MOTOR

BMS COMMUNICATIONS (STD)

- BACNET (STANDARD)
- LONWORKS (OPTIONAL)

REQUIRED WIRING:

-DIGITAL ON/OFF (THRU COMM)
-SPEED REFERENCE (THRU COMM)
-NOZZLE FEEDBACK (HARDWIRE)
-ALARM (THRU COMM)
-FAN FLOW (THRU COMM)

BMS SYSTEM

SUPPLIED BY OTHERS

DUCT PRESSURE

SIGNAL COMPONENT

BY OTHERS

BYPASS DAMPER

COMPONENT

BY OTHERS

ACTUATOR 4

ADDITIONAL NOZZLE ACTUATORS
QTY. DEPENDENT ON UNIT SIZE

ACTUATOR 3,4,5

TRANSDUCER/TERMINAL
ENCLOSURE
- AT THE FAN

ACTUATOR 2

ACTUATOR 1

NOZZLE POSITION
FEEDBACK TO BMS

FAN PRESSURE (LOW&HIGH)

TO SURE-AIRE CONNECTION
PLATE ON FAN

ABB BYPASS MODULE

DIGITAL RELAY OUT
CLOSE WHEN FAN ON

ABB DRIVE MODULE

SURE AIRE

VARIABLE N.

U I

1
2

ANALOG INPUT

SIGNAL SWITCH

VGN PCB

CBL#1 (BLACK)

CBL#1 (WHITE)

CBL#2 (WHITE)

CBL#2 (BLACK)

SHIELD

CBL#3 (RED)

CBL#3 (BLACK)

CBL#3 (ORANGE)

CBL#3 (ORANGE)

SET DIP
SWITCHES

POWER SUPPLY

FUSE

DRIVE DISCONNECT LOAD SIDE

FACTORY WIRING

FIELD WIRING

ABB ECLIPSE DRIVE WITH VGN TECHNOLOGY

+24DC

COM

COM

COM

NOZVDC

SURAIR

ISOPWR

GND

GND

NOZFB1

NOZFB2

+24DC

+24DC

NOZZLE ACTUATOR FEEDBACK RECOMMEND 1 PER SHAFT

MAY BE MULTIPLE ACTUATORS PER NOZZLE BLADE SHAFT

TB1

Nozzle VDC
Sure-Aire VCD
Isolation Power
Manual Switch 1
Manual Switch 2
+24 Volts
+24 Volts
+24 Volts
Common
Common
Common

1
5
14
16
AI1
AGND
AO1

TB2

Power Supply +
Common

R1

13

VGN Technology

®