1

Initial Setup Menu Parameters

Parameter Name Values

Default

Description

Units

Imperial, Metric

Imperial

Units used for settings within controller

Control Mode

Constant Pressure,

Constant Airflow

Constant pressure

This sets the main function of the control.

Setpoint Location

Local, Remote

Local

Determines where the pressure or airflow setpoint will be set.

If local, set using the setpoints menu. If remote, connect a 0-10V signal to

remotely set the setpoint.

Min Pressure/Flow

Setpoint

Bottom end of pressure

transducer span

This value will correspond to the minimum voltage (0 or 2V) from the

remote setpoint signal. Only available when setpoint is set to [remote].

Max Pressure/Flow

Setpoint

Top end of pressure

transducer span

This value will correspond to a 10V signal from the remote setpoint signal.

Only available when setpoint is set to [remote].

Remote Setpoint

Voltage

0-10V, 2-10V

0-10V

Change this setting based on the signal for the remote setpoint. If 0-10V,

0V refers to the minimum setpoint. If 2-10V, 2V refers to the minimum

setpoint. Only available when setpoint is set to [remote].

Fan Inlet/Outlet

Inlet, Outlet

Inlet

Set this parameter to match where the pressure probe is located in relation

to the fan the control is controlling. Only available in [pressure] mode.

Duct Area

0-100 sq. ft

(0-9.29 sq. m)

4 sq ft

(0.37 sq. m)

Input the area of the duct where the pitot tube is located. If using an AMS,

input the area from the AMS label. Only available in [airflow] mode.

Measurement Device Pitot Tube, AMS

Pitot Tube

Select the measurement probe type being used. Only available in [airflow]

mode.

AMS “K” value

When AMS is used, set to “K” value on AMS label.

Only available in [airflow] mode.

AMS “m” value

When AMS is used, set to “m” value on AMS label.

Only available in [airflow] mode.

Pitot Correction

Factor

0.50 to 2.00

1.00

Corrects the airflow measurement for the airflow device being used.

Adjust the value if using a pitot tube by others. Only available in [airflow]

mode.

Air Density Correction

Factor

0-5.00

1.00

Adjust this value to match the density of the air flowing through the

system. Select the value from the table on pg. 11.

Only available in [airflow] mode

Max Flow Output

0-100,000 CFM

0-m

3

/hr 169,901

500 CFM

8495 m

3

/hr

Sets the top of the span for the reference output in [airflow] mode. Adjust

this setting to give more resolution to the remote airflow reading.

Pressure/Airflow

Output

0-10V, 2-10V

0-10V

This sets the span of the reference output.

Remote Sensor Min

Pressure

-1.00 in. WC (-249Pa)

Set this value to the minimum pressure value of the remote pressure

transducer. Only available with remote pressure transducer model.

Remote Sensor Max

Pressure

1.00 in. WC (249Pa)

Set this value to the minimum pressure value of the remote pressure

transducer. Only available with remote pressure transducer model.

Control output

0-10V, 2-10V

0-10V

This value will change the span of the control output.

Vari-Green motors use 0-10V.

Startup Timer

1-30 Seconds

3 Seconds

The control output will be set to the minimum value at startup for this

amount of time.

Sensor Filter

0-10 Seconds

0

Adjust this value if the pressure reading is unstable.

Increasing the value increases the stability of the pressure reading.

Response Time

Fast, Medium,

Slow

Fast

This value adjusts the response time of the controller.

Set to Medium or Slow if the fan is unstable/oscillating.

Constant Pressure Control

7